english
1. TECHNICAL DATA
As a stove of construction type 1, it is possible to connect it
to the chimney together with an existing other stove or
another hearth for solid fuels, as long as the chimney
dimensioning complies with DIN 4705, Part 3.
TECHNICAL DATA
Height [mm]
Width [mm]
Depth [mm]
Weight [kg]
Flue pipe outlet-Ø [mm]
Nominal heating output [kW]
Max. heating capacity [kW]
Min. heating capacity [kW]
Room heating capacity (depen-
ding on building insulation) [m³]
2. IMPORTANT INFORMATION
The installation and operation information given here is of
general nature. National and European standards, local and
building regulations as well as fire prevention laws must be
observed during the operation of the stove.
General safety instructions for the
operation of your stove
•
Read the entire manual before starting up your stove
thoroughly and observe the caution notices.
•
Your heating unit must not be moved without approved
means of transport with sufficient load-bearing capacity.
•
Your heating unit is not suitable to be used as a stand or
as a ladder.
•
Please keep in mind that your
stove's surface heats up considerably
during
operation.
We
recommend wearing a safety mitten
when operating your stove.
•
Attention – stove varnish is no rust prevention!
•
Make your children aware of this particular danger and
keep them at a distance from the heating unit whenever it is
in operation.
•
Only burn approved fuels and materials as listed in the
chapter "Clean Burning".
•
The burning or placing of flammable or explosive
materials, like empty spray cans, etc. into the firebox as well
as the storage of such materials in the immediate vicinity of
your heating unit is strictly forbidden due to the danger of
explosion.
•
Do not wear loose or flammable clothing when adding
fuel to the fire.
•
Placing non-heat-resistant objects on the heating unit or
in the vicinity of the heating unit is forbidden.
Woody
Woody Xtra
1027
1127
538
538
399
399
135
258
130
130
6
6
8
8
3,5
3,5
65–165
65–165
therefore
5
Exhaust values for multiple use of the chimney in
accordance with DIN 4705, Part 3 and for the calculation of
the chimney measurements in accordance with DIN 4705,
Part 2
Fluegas mass flow
Fluegas temperature
Minimum feed pressure
Nominal thermal output
•
Do not lay laundry onto the stove for drying. Laundry
hung up to dry must be kept at a safe distance from the
stove because of the danger of fire.
•
The wood stove is not suitable for long term heating.
•
During the operation of your heating unit it is forbidden to
use flammable or explosive materials in the same or an
adjacent room to the one in which your heating unit is
located.
•
The appliance must be operated with the stove door
closed.
•
The stove door and all fittings for adjusting the stove
must be closed, if the appliance is out of use.
Setting up your stove
Required safety distances
see name plate - in Fig. 1)
a – toward the front in the radiated area > 1200 mm
b – to the side > 260 mm
c – to the back > 200 mm
Corner installation:
a – toward the front in the radiated area >1200 mm
b – to the side > 200 mm
Make sure that the room in which the stove is set up has at
least one door or window into the outside or is directly
adjacent to such a room. Other fireplaces and extractor
hoods must not be operated in the same room as the stove.
Floor load capacity
Make sure that the load capacity of the supporting
construction is sufficient to carry the weight of the entire
unit, before the heating unit is installed.
WOODY / WOODY Xtra
5,78 g/s
294 °C
convection air open
12 Pa
at 0.8 times n.
10 Pa
ther. outp.
(Minimum distances –