EXAMPLE
The display shows: "WATER" and an "alarm" triangle.
Use of Humidifier: cause no water supply, or no increase in RH% measurement by SHC80. Actions: check
that the tap is open, check that the valve is working by turning off power to the Evap system module and
switching it on again. Listen to see whether water is flowing for min 20 seconds.
RESET procedure:
•
Activate LCD by pressing
menu.
•
Display shows STPT.
•
Use the arrow buttons to scroll through the menu
•
If the display shows ALARM, press
display shows AL02. Press
•
Press arrow buttons until display shows Rst.
•
Confirm reset by pressing
•
Check reset by pressing
The 'water' and 'alarm' triangle should now have disappeared.
•
Section 3 – Faults and alarms
mode
, wait 2 seconds, press
mode
. Display indicates AL01, press the arrow buttons until the
mode
- the display shows NO
mode
and then the
mode
again.
Evap controller
mode
again for 2 sec to go to the reset
button
7