From serial number BR2018-H-00025
Alarm LED
Display
Tekst
OFF
Alarm LED on
M OFF
Alarm LED
SENSUP
blinks
3 times
Alarm LED
OUTDEF
blinks
5 times
Alarm LED
WATER
blinks
9 times
Alarm LED
HEATER
blinks
15 times
Alarm LED
AIRFLW
blinks
17 times
Section 3 – Faults and alarms
Meaning
Action
Measured
outside
temperature
above set point
TS04
Contact main
Restore contact main enable, see
enable broken,
wiring diagram
unit switches off
Contact with
Check SHC80 wiring and if
SHC80 sensor
necessary repair, check that the
broken
light on SCH80 sensor flashes
regularly, if not replace faulty
sensor.
T3 sensor
Check wiring for break or wear, in
outside air faulty
case of doubt replace sensor.
No rise of RH in
- Check that the water tap is
duct
open.
If the valve is open and there is a
demand (outside temperature
below 12°C), check the screen in
the connection coupling, which
must be clean.
- Check the operation of the water
valve. Disconnect the black
supply hose from the knee on the
unit, and reset the unit by
unplugging and re-inserting the
unit; if water comes out and the
water valve stops after 90
seconds, the valve is fine, the
water continues to flow or no
water comes out of the hose, the
water valve is defective, replace
the water valve. If the water valve
works and the matrix does not get
wet after the valve has been
switched, the Legionella filter is
clogged; replace the cassette.
If the matrix gets wet and still an
alarm, then the matrix is dirty and
the cassette needs to be
replaced.
No.: 351025
Heating faulty
Check air temperature after the
humidifier, this must be >8ºC, if
not air heater is faulty. Call
installer for replacement.
No airflow
Check if HRV is working.
Evap controller
Reset
Automatically
Automatically
Automatically
Automatically
Automatically
Automatically
5