Beha-Amprobe ALC-110-EUR Manuel De L'utilisateur page 19

Pince de mesure de courant de fuite

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 84
Battery life
Low battery voltage
Low battery
indication
Auto power off
Dimensions
(H x W x L)
Weight
ELECTRICAL SPECIFICATIONS
Accuracy is given as ± (% of reading + counts of least
significant digit) at 23 °C ± 2 °C (≤ 80% R.H.)
AC Function
• AC A specifications are AC coupled, true RMS.
• For non-sinusoidal waveforms, Additional Accuracy by
Crest Factor (C.F.):
Add 1.0% for C.F. 1.0 to 2.0
Add 2.5% for C.F. 2.0 to 2.5
Add 4.0% for C.F. 2.5 to 3.0
• Max. Crest Factor of Input Signal:
3.0 @ 3000 counts
2.0 @ 4500 counts
1.5 @ 6000 counts
• Frequency Response is specified for sine waveform.
• When operating under magnetic field add error E11.
• When measuring leakage current of multiple conductors,
add error E12 for influence of load current.
• For Position Error see error E1.
AC Current
Range
15 to 40 Hz
[1]
6 mA
±(5.0%+5D) ±(2.0%+5D) ±(1.0%+5D) ±(2.0%+5D)
60 mA
±(5.0%+5D) ±(2.0%+5D) ±(1.0%+5D) ±(2.0%+5D)
600 mA ±(5.0%+5D) ±(2.0%+5D) ±(1.0%+5D) ±(2.0%+5D)
6 A
60 A
Minimum Reading is 0.010 mA
[1]
Frequency response is 60 Hz to 10 kHz.
[2]
When frequency > 1 kHz, add 0.5% to accuracy.
Minimum Resolution: 0.001 mA
60 hours typical
Approx. 2.5 V
Idle for 20 minutes
221 x 89 x 48 mm
(8.7 x 3.5x 1.8 in)
Approximately 410 g (0.90 lb)
with battery installed
40 to 50 Hz
-
±(2.0%+5D) ±(1.0%+5D) ±(2.0%+5D)
-
±(2.0%+5D) ±(1.0%+5D) ±(2.0%+5D)
Accuracy
50 to 60 Hz
15
60 to 1 kHz
[2]
[2]
[2]