Function and features
The slave receives data via the AS-Interface and converts them into
analogue output signals. The AS-i module operates as a slave with
bidirectional data transfer in the AS-i network.
The data transfer from the host to the slave is asynchronous according
to the AS-i profile S-7.3 and the AS-i specification V2.1.
• Current output 0..20mA (AC2218)
or voltage output 0..10V (AC2219)
• AS-i profile S-7.3.6
• The actuators are connected via Combicon connectors
(accessories, e. g. E70230)
• Maximum number of modules per AS-i system: 31
• R
for current output 600Ω; R
max
• Time for converting the measured values in the slave
- for four channels: <1ms
• Actuator supply from AS-i (max. 90mA) or external 24V PELV volt-
age source (the external supply voltage is selected automatically as
soon as an external voltage is applied)
• 16 bits /1µA (AC2218) or 16 bits /1mV (AC2219)
Addressing
Assign a free address between 1 and 31, the address set at the facto-
ry is 0.
Address the slave with the addressing unit AC1144.
The module can be addressed when mounted and wired with the
addressing cable (E70213) via the implemented addressing interface.
Addressing via the addressing socket is only allowed when dis-
connected.
for voltage output >1kΩ
min
9
PAGE