Tableau Etendue De Mesure; Codification De L'instrument - ASCON TECNOLOGIC TLK41 Instructions Pour L'utilisation

Regulateur electronique digital a microprocesseur
Table des Matières

Publicité

-
7.5
TABLEAU DE L'ETENDUE DE MESURE
ENTREE
tc J
-160... 1000°C
"HCFG" = tc
- 256... 1832°F
"SEnS" = J
tc K
-270... 1370°C
"HCFG" = tc
- 454... 2498°F
"SEnS" = CrAl
tc S
"HCFG" = tc
"SEnS" = S
Pt100 (IEC)
"HCFG" = rtd
-328... 1562°F
"SEnS" = Pt1
PTC (KTY81-121)
"HCFG" = rtd
"SEnS" = Ptc
NTC (103-AT2)
"HCFG" = rtd
"SEnS" = ntc
0..20 mA
"HCFG" = I
"SEnS" = 0.20
4..20 mA
"HCFG" = I
"SEnS" = 4.20
0... 50 mV
"HCFG" = UoLt
"SEnS" = 0.50
0... 60 mV
"HCFG" = UoLt
"SEnS" = 0.60
12... 60 mV
"HCFG" = UoLt
"SEnS" = 12.60
0... 5 V
"HCFG" = UoLt
"SEnS" = 0.5
1... 5 V
"HCFG" = UoLt
"SEnS" = 1.5
0... 10 V
"HCFG" = UoLt
"SEnS" = 0.10
2... 10 V
"HCFG" = UoLt
"SEnS" = 2.10
ASCON TECNOLOGIC - TLK 41 - INSTRUCTIONS POUR L'UTILISATION - Vr. 03 – ISTR-MTLK41FRA03 - PAG. 14
"dP" = 0
"dP"= 1, 2, 3
-160.0... 999.9°C
-199.9... 999.9°F
-199.9... 999.9°C
-199.9... 999.9°F
-50... 1760°C
-50.0... 999.9°C
-58... 3200°F
-58.0... 999.9°F
-200... 850°C
-199.9... 850.0°C
-199.9... 999.9°F
-55... 150°C
-55.0... 150.0°C
-67... 302°F
-67.0 ...302.0°F
-50... 110°C
-50.0... 110.0°C
-58... 230°F
-58.0... 230.0°F
-199.9... 999.9
-1999... 9999
-19.99... 99.99
-1.999... 9.999
-199.9... 999.9
-1999... 9999
-19.99... 99.99
-1.999... 9.999
-199.9... 999.9
-1999... 9999
-19.99... 99.99
-1.999... 9.999
-199.9... 999.9
-1999... 9999
-19.99... 99.99
-1.999... 9.999
-199.9... 999.9
-1999... 9999
-19.99... 99.99
-1.999... 9.999
-199.9... 999.9
-1999... 9999
-19.99... 99.99
-1.999... 9.999
-199.9... 999.9
-1999... 9999
-19.99... 99.99
-1.999... 9.999
-199.9... 999.9
-1999... 9999
-19.99... 99.99
-1.999... 9.999
-199.9... 999.9
-1999... 9999
-19.99... 99.99
-1.999... 9.999

7.6 - CODIFICATION DE L'INSTRUMENT

TLK 41 a b c d e f g h ii
a: ALIMENTATION
L = 24 VAC/VDC
H = 100... 240 VAC
b: SORTIE OUT1
R = A relais
O = Sortie en tension VDC pour SSR
c: SORTIE OUT2
R = A relais
O = Sortie en tension VDC pour SSR
- = Non présente
d: SORTIE OUT3
R = A relais
O = Sortie en tension VDC pour SSR
- = Non présente
e: SORTIE OUT4 (doit être du même type que OUT3)
R = A relais
O = Sortie en tension VDC pour SSR
- = Non présente
f: INTERFACE DE COMMUNICATION
S = Interface Sérielle RS 485
- = Aucune Interface
g: ENTREE POUR TRANSFORMATEUR AMPEROMETRIQUE
H = Présente
- = Non présente
h: SONDES EN OPTION
- = Aucune
ii = CODES SPECIAUX
TLK 41 PASSWORD = 381

Publicité