Ref
Text
AL_20
Maintenance
Alarm for compressor
compressor
maintenance default at
90,000 hours of operation
AL_22
Maintenance
Alarm for maintenance
pump
default pump at 90,000
hours of operation
AL_29
Fault com. CpCOe Communication alarm with
CpCOe1
AL_30
CpCOe config.
Improper configuration of
error
CpCOe1
AL_V06
Low overheating
Low overheating
AL_V16
Alarm LOP EVD1
Automatic generated by
alarm editor
AL_V17
EVD1 MOP alarm Automatic generated by
alarm editor
AL_V18
Hte temp.
Automatic generated by
condensation
alarm editor
AL_V03
Low suction temp. Low suction temperature
AL_V19
EEV motor error
Automatic generated by
alarm editor
AL_V20
Auto-tunning
Automatic generated by
impossible
alarm editor
AL_V21
EXV closure urgent Automatic generated by
alarm editor
AL_V22
EXV DeltaT alarm Delta temperature (EVD 1) no action
AL_V23
EXV DeltaP alarm Delta pressure (EVD 1)
AL_V24
EXV config.
Automatic generated by
err.EXV
alarm editor
AL_V25
Manual pos. config.
Automatic generated by
error POS. manual
alarm editor
AL_V26
EXV number
Automatic generated by
config. error
alarm editor
AL_28
Fault com.
Compressor comm fault
compressor
alarm
AL_ABB1 ABB comp. var. sp.
Alarm connected to ABB
drive alarm
compressor's variable-
CF visualization
frequency drive
V18
AL_ABB2 ABB comp. var. sp.
Warning related to ABB
drive warning
compressor's variable-
CF visualization
frequency drive
V18
AL_ABB3 ABB pump var. sp.
Alarm related to the ABB
drive alarm
pump's variable-frequency
Cf. visualization
drive
V19
AL_ABB4 Warn. ABB pump
Warning related to ABB
var. sp. drive
pump's variable-frequency
Cf. visualization
drive
V19
AL_VAR_
Var. sp. drive
Bad firmware version in the
01
firmware, pump
compressor's variable-
Cf. menu I04
frequency drive
AL_VAR_
Var. sp. drive
Bad firmware version in the
02
firmware, comp.
pump's variable-frequency
Cf. menu I04
drive
Version: 2020-01
Control User Manual
Description
degraded mode
no action
no action
Complete shutdown
No action
no action
no action
no action
no action
no action
no action
no action
no action
no action
no action
no action
no action
Complete shutdown
Compressor stop
no action
Complete shutdown
no action
Unit stop
Unit stop
TECUMSEH EUROPE S&L
2 av. Blaise Pascal, 38090 Vaulx Milieu
Tel. : +33 (0)4 74 82 24 00 - www.tecumseh.com
INFINEE chillers
Comments
Degraded
of pump and
mode
compressor
no
no
no
no
no
yes
no
no
no
no
no
no
no
no
no
no
no
no
no
no
no
no
no
no
no
no
no
no
no
no
no
no
no
no
no
yes
no
no
no
no
no
yes
no
no
no
yes
no
yes
Stop
Compressor
stop
no
no
yes
no
no
no
no
no
no
no
no
no
no
no
no
no
no
yes
o
no
yes
no
yes
yes
ENGLISH
- 32 -