Ref
Text
AL_S02
LP pressure switch
LP switch out of order or
out of order or
tripped
disconnected
pressure switch open and
LP > LP_PreAlrm_Thrsh
(0.5 bar)
This is not a triggering of
LP due to an empty circuit
AL_S03
LP alarm
Software triggering of LP
Software triggering
threshold overshooting
LP < LP_Alrm_Thrsh (0.5
bar)
AL_S04
Trig. LP pressure
Triggering of the LP switch
switch
upon overshooting of
Low pressure
pressure threshold (normal
triggering of pressure
switch)
AL_S05
LP default alarm
LP fault alarm
Pressure too low
LP switch closed and
LP < LP_Alrm_Thrsh (-0.5
bar)
Under pressure without
tripping pressure switch
AL_S06
HP pressure switch
HP pressure switch out of
out of order or
order or disconnected
disconnected
Open HP switch and
HP < HP_PreAlrm_Thrsh
(21.0 bar)
This is not a triggering of
HP due to overpressure
AL_S07
HP alarm
Software triggering of HP
Software triggering
threshold overshoot
HP > HP_Alrm_Thrsh (21.6
bar)
AL_S08
Trig. HP switch
Triggering of the HP switch
High pressure
upon overshooting of
pressure threshold (normal
triggering of the pressure
switch)
AL_S09
HP fault alarm
HP fault alarm
Pressure too high
HP switch closed and
HP > HP_Alrm_Thrsh (22.6
bar)
Overpressure without
tripping pressure switch
AL_V01
General alarm
General alarm compressor
Start-up
start-up fault
PK – Po < 3 bar
compressor
and compressor running
Version: 2020-01
Control User Manual
Description
degraded mode
Switch to stop mode
Antifreeze mode possible
Compressor stop and
restart allowed on the first
2 threshold overshoots,
on third triggering, fault
indication and complete
compressor shutdown
Condenser fan override
at 100% for 3 hours
Switch to stop mode
Antifreeze mode possible
Switch to stop mode
Antifreeze mode possible
Switch to stop mode
Antifreeze mode possible
Compressor stop and
restart allowed on the first
2 threshold overshoots,
on third triggering, fault
indication and complete
compressor shutdown
Condenser fan presetting
at 100% for 3 hours
Compressor stop
Limits compressor
frequency to 40 Hz for 3
hours
Switch to stop mode
Antifreeze mode possible
Switch to stop mode
Antifreeze mode possible
TECUMSEH EUROPE S&L
2 av. Blaise Pascal, 38090 Vaulx Milieu
Tel. : +33 (0)4 74 82 24 00 - www.tecumseh.com
INFINEE chillers
Comments
Degraded
of pump and
mode
compressor
no
yes
yes
no
no
yes
no
yes
no
yes
yes
no
yes
no
no
yes
no
yes
Stop
Compressor
stop
yes
yes and
automatic
restart
yes
yes
yes
yes and
automatic
restart
no
yes
yes
ENGLISH
- 30 -