Ref
Text
AL_V02
Fault in variable-
Compressor's variable-
frequency drive
frequency drive fault alarm
compressor
Compressor stationary and
current consumed > 1 A
AL_V04
Detect. coolant leak Coolant leak detection
AL_V07
High discharge
High discharge
temp.
temperature alarm
Discharge T°C >
"Thrsh_High_Tref" (120°C)
AL_V08
Repeated HP
Repeat HP offloading
offloading
Counting of the 3 faults
3 software trigger.
"AL_PHP_Soft.Trigger"
AL_V09
Water pump fault
Water pump fault
Delta P calculated <
Thrsh_DeltaP_Al_pump
(0.5 bar)
and no comm pump error
AL_V10
Fault water flow
No delta between the input
too low
pressure of the unit and the
inlet pressure of the pump
no water flow
DeltaP < 0.5 bar
AL_V11
Water loop fault
Check for pressure drop on
Water leak
water inlet or outlet >
Thrsh_decr_P (5.0 bar)
AL_V12
Water loop fault
Water control loop fault
Pressure < cons
water flow
min
Pressure at unit input or
pressure at pump inlet <
0.5 bar
AL_V13
Inversion of
T °C sensors inverted
sensors
water inlet and outlet
W_OutTemp – W_InTemp
Water I/O
temperature
> 1.0°C with compressor
running
AL_V14
Water loop fault
Water control loop fault
Pressure > cons
water pump overload
max
Pressure at unit outlet or
pressure at unit inlet or
pressure at pump inlet > 10
bar
AL_V15
Antifreeze fault
Antifreeze fault
Pump offline and antifreeze
mode activated
AL_16
Fault com. pump
Modbus communication
error with the pump's
variable-frequency drive
Al_18
Evap. temp. too low Temperature too low at
evaporator output
Temperature calculated
according to pressure and
type of fluid
"T_Sat_Out_exchange" <
"Low_Thrsh_T_Sat_Out_E
xchange" (between -10°C
and -35°C depending on
the glycol level)
Version: 2020-01
Control User Manual
Description
degraded mode
Complete shutdown
Switch to stop mode
Antifreeze mode possible
No compressor stop
Valve override 100%
Compressor limit to 60
Hz
Compressor stop
Limits compressor
frequency to 40 Hz for 4
hours
Forces ventilation
frequency to 100% for 4
hours
Complete shutdown
Complete shutdown
Complete shutdown
Complete shutdown
Switch to stop mode
Antifreeze mode possible
Complete shutdown
Already an alarm in an
offline pump case
Complete shutdown
Switch to stop mode
Antifreeze mode possible
Restarting after the first
two triggers
at the third trigger, need
an acknowledgment to
restart
TECUMSEH EUROPE S&L
2 av. Blaise Pascal, 38090 Vaulx Milieu
Tel. : +33 (0)4 74 82 24 00 - www.tecumseh.com
INFINEE chillers
Comments
Degraded
of pump and
mode
compressor
no
yes
no
yes
yes
yes
yes
yes
no
yes
no
yes
no
yes
no
yes
no
no
no
yes
no
yes
no
yes
no
no
Stop
Compressor
stop
yes
yes
yes
yes
yes
yes
yes
yes
yes
yes
yes
yes
yes
ENGLISH
- 31 -