Settings menu
Setting of setpoints and certain operating parameters. Accessible through the "User" password
Request a password.
Enter the User password to access the following
windows.
The developer password also allows access to
this menu.
Select the glycol level used on the water circuit.
Menu 1
Attention: the glycol level allows different
Co01
operating regimes on the water temperature.
Menu 2
Setting the temperature setpoint on the water
Co02
return.
Menu 3
Adjusting the desired temperature delta between
Co03
the water return and the water outlet.
Display of the setpoints according to the
Menu 4
parameters set above.
Co04
No modification possible
Menu 5
Adjustment of the offset around the setpoint for
Co05
starting up and stopping the compressor.
Display of the setpoints according to the
Menu 6
previously set parameters.
Co06
No modification possible.
Menu 7
Adjusting the compressor operating frequencies:
Co07
operating range between 25 Hz and 85 Hz.
Menu 8
Setting the NO or NF output type for alarm return
Co08
and compressor start-up indication