INSTALLATION DISTANCE: 600-1
B
B
B
50
50
50
INSTALLATION DISTANCE
A
A
A
A
A
A
50
50
B-B
B-B
50
B-B
350
350
350
A non-flammable panel must be fitted directly above the
convection opening so that "standing" hot air does not
develop above the convection opening. This is done to
protect the ceiling and to transport the heat out of the
fireplace insert.
B
B
B
The insulated part of the chimney must extend all the way
down to the flue spigot.
DISTANCE FROM
Furniture to door
Panels to fireplace insert
Ceiling to door top edge
Ceiling from convection
opening
Floor to door bottom edge
Flammable at side of door
Firewall extension
A-A
A-A
A-A
DISTANCE IN MM
1100
50
1000
500
300
350
475