WARNING: the installation of the device must be exclusively done by
qualified personnel, following the regulations in force and the
guidelines for KNX installations.
1. The length of the bus line between the actuator and the power supply unit must not
exceed 350 metres.
2. The length of the bus line between the actuator and the most distant KNX device
must not exceed 700 metres.
3. To avoid unwanted signals and overvoltages do not use ring circuits.
4. Keep a distance of at least 4 mm between the individually insulated cables of the bus
line and those of the electric line (figure C).
5. Do not damage the electrical continuity conductor of the shielding (figure D).
WARNING: the unused bus signal cables and the electrical continuity
conductor must never touch elements under power or the earth
conductor!
WARNING: cut off mains power before connecting the device to the
electricity mains!
Figure B shows the electrical connections diagram.
1. Connect the bus cable's red wire to the terminal's red connector (+) and the black
wire to the black connector (-). Up to 4 bus lines (wires of the same colour in the same
connector) can be connected to the terminal (figure E).
2. Insulate the screen, the electrical continuity conductor and the remaining white and
yellow wires of the bus cable (should a bus cable with 4 conductors be used), which
are not needed (figure D).
3. Insert the bus connector into the special feet of the device. The fastener guides
determine the direction it should be inserted. Insulate the bus terminal using the
relative cover, which must be screwed onto the device.
The cover guarantees that the power cables and the bus cables are separated by at
least 4 mm (figure F).
4. Connect the loads to the relative screw terminals on the back of the actuator (Figure
G), checking that they do not exceed the current limits indicated in the Technical
Specifications.
INSTALLATION
Warnings for KNX installations
Electrical connections
19