Explanation of thresholds and hysteresis:
EN
The monitoring period by the sensors is fixed at 10 minutes (to change this value, contact the Technical Support Department).
The settings associated with this mode of operation are:
The transmission periodicity (zero in this usage situation) (register 301).
The presence and type of external sensor (registers 302 and 304).
The configuration of the events (registers 303 and 305).
The high alarm threshold channel A (register 309).
The high alarm hysteresis channel A (register 310).
The low alarm threshold channel A (register 311).
The low alarm hysteresis channel A (register 312).
The high alarm threshold channel B (register 313).
The high alarm hysteresis channel B (register 314).
The low alarm threshold channel B (register 315).
The low alarm hysteresis channel B (register 316).
A complete list of the registers can be found in paragraph 3.4.
E.g.:
Register
S301
S302
S304
S303
S305
S309
Value encoding
Value
Decimal
0
Hexadecimal
0x02
Hexadecimal
0x01
Hexadecimal
0x03
Hexadecimal
0x02
Decimal
1 200 000
Result
Event mode
Channel A configured for a sensor 4-20mA
Channel B configured for a sensor 0-10V
On channel A:
Detection of high and low thresholds
Detection of event on disabled digital input
No waiting period
On channel B:
Detection of high thresholds
Detection of event on disabled digital input
No waiting period
The value of the high threshold of channel A is:
1 200 000x10=12 000 000nA so 12mA