LED EMERGENCY LIGHTS
TECHNICAL DATA
Model
VT-522-S
Wa�s
2
No. Of Led
16
Lumens
140
Working Time
>3 Hours
PC
Body Type
IP Ra�ng
IP20
Emergency Opera�on
>3 Hours
(Maintained)
Time
Charging Time
12 Hours
Ba�ery Charging
100-140mA
Current
Ba�ery Discharge
200-280mA
Current
Ba�ery Type
Ni-Cd 3.6V,900mAh
Dimension
355x46x200mm
Input Power
AC:220-240V,50/60Hz
INTRODUCTION & WARRANTY
Thank you for selecting and buying V-TAC product. V-TAC will serve you the best. Please read these instruc-
tions carefully before starting the installing and keep this manual handy for future reference. If you have any
another query, please contact our dealer or local vendor from whom you have purchased the product. They
are trained and ready to serve you at the best. The warranty is valid for 3 years from the date of purchase.
The warranty does not apply to damage caused by incorrect installation or abnormal wear and tear. The
company gives no warranty against damage to any surface due to incorrect removal and installation of the
product. The products are suitable for 10-12 Hours Daily operation. Usage of product for 24 Hours a day
would void the warranty. This product is warranted for manufacturing defects only.
3
*
WARRANTY
ENGLISH
WARNING:
• This product must be disconnected from the circuit if subjected to any high voltage or insulation resistance
testing. Irreparable damage will occur if this instruction is not followed
• Recommended routine test procedure in accordance with BS5266
• Daily check – check that the status GREEN LED indicator is illuminated
• Monthly functional test – simulate a mains supply failure for approx. 30 secs by operation of key switch or
switching off a circuit breaker. Ensure normal supply is restored after test and the indicator status LED is
illuminated
• Twice yearly conduct a one hour duration test - simulate a mains supply failure for one hour continuous test
by operation of key switch or switching off circuit breaker. Ensure normal supply is restored after test and the
indicator status LED is illuminated
• Annual full three hour duration test - conduct a three hour continuous duration test. Simulate a mains supply
failure for three hour continuous test by operation of key switch or switching off circuit breaker. Ensure normal
supply is restored after test and the indicator status LED is illuminated
• Please make sure to turn off the power before starting the installation.
• The light source of this luminaire is not replaceable; when the light source reaches its end of life the whole
luminaire shall be replaced.
• Replace any cracked protective shield.
• Installation should only be done by a certified electrician.
• For Indoor Use only
SAFETY
• Installation of this luminiare should only be carried out by a qualified electrician or competent person to the
current IEE Wiring Regulations (BS7671)
• Please isolate main prior to installation/maintenance.
• Check the total load on the circuit cable, fuse or circuit breaker.
• This product is Class II double insulated
This marking indicates that this
product should not be disposed
of with other household wastes.
Caution, risk of electric shock.
INSTALLATION:
• Provide power to the required point of installation
• Cut a suitable aperture in the ceiling as per the cut-out details in Fig 1 ensuring that it does not infringe with
electical cables, water/gas pipes or ceiling joists.
ENGLISH
MULTI-LANGUAGE
MANUAL QR CODE
Please scan the QR code
to access the manual in
multiple languages.
48mm
310mm
FIG1
• Remove 2 screws on top of the fitting (see Fig 2)
• Connect the battery to the inverter via the plug and socket provided.
EMERGENCY TERMINATIONS MAINTAINED/NON-MAINTAINED
• When all connections have been made reassemble the fitting completely.
• Restore the supply and check that the Green LED indicator illuminates to confirm the batteries are charging.
There are three possible reasons when the green LED indicator does not light up:
1) there is no power supply AC220-240V,
2) the batteries are not properly connected to the PCB,
3) the batteries are not being charged.
• Allow a short period for partly charging the batteries and then isolate the mains supply to the fitting in order
to check the correct operation of the fitting in emergency mode. After 36 hours on continuous charge (and only
at a safe time) a mains failure should be simulated to ensure that the fitting illuminates for its rated emergency
duration.
The luminaire will have a 1-hour backup after 14 hours charging and will be fully charged after 24 hours (first
charge 36 hours)
MAINTENANCE
Once the luminaire no longer meets the rated emergency operation the batteries must be replaced after a
maximum of 4 years in service.
Repairs should only be carried out by a qualified person. Please recycle disposal of replaced components where
facilities exist. Special care should be taken if it's required to open the fitting as the fitting may still be "live"
even though the mains supply has been isolated. In these circumstances immediately disconnect the battery
supply.
Servicing and cleaning should only be carried out after the fitting has been made electrically safe. Cleaning of
luminaires should be carried out at regular intervals not only to ensure good optical performance but also
ensure that dirt does not accumulate to such an extent as to impair the electrical or thermal safety of the
fitting.
IN CASE OF ANY QUERY/ISSUE WITH THE PRODUCT, PLEASE REACH OUT TO US AT: SUPPORT@V-TAC.EU
FOR MORE PRODUCTS RANGE, INQUIRY PLEASE CONTACT OUR DISTRIBUTOR OR NEAREST
DEALERS. V-TAC EUROPE LTD. BULGARIA, PLOVDIV 4000, BUL.L.KARAVELOW 9B
ENGLISH
1. Remove 2-PIN connector for
Non-Maintained Operation
2. Connect battery lead

Publicité

loading

Sommaire des Matières pour V-TAC VT-522-S

  • Page 1 Once the luminaire no longer meets the rated emergency operation the batteries must be replaced after a • Provide power to the required point of installation Thank you for selecting and buying V-TAC product. V-TAC will serve you the best. Please read these instruc- maximum of 4 years in service.
  • Page 2 Ако осветителното тяло вече не може да осигури номиналния период на аварийна работа, батериите Благодарим ви, че избрахте и закупихте продукт на Ви-Тек (V-TAC). Ви-Тек (V-TAC) ще ви послужи по • Изрежете подходящ отвор на тавана според детайлите на фигурата на фигура 1, като се уверите, че той...
  • Page 3 Una volta che l'apparecchio non soddisfa più il funzionamento di emergenza nominale, le batterie devono essere Grazie per aver scelto e acquistato il prodotto della V-TAC. La V-TAC Le servirà nel miglior modo possibile. Si • Fornire alimentazione al punto di installazione desiderato.
  • Page 4 össze olyan mértékben, hogy rontsa a termék elektromos vagy hőbiztonságát. 310mm IN CASE OF ANY QUERY/ISSUE WITH THE PRODUCT, PLEASE REACH OUT TO US AT: SUPPORT@V-TAC.EU FIG1 FOR MORE PRODUCTS RANGE, INQUIRY PLEASE CONTACT OUR DISTRIBUTOR OR NEAREST DEALERS.
  • Page 5 Sobald die Leuchte den Nennnotbetrieb nicht mehr erfüllt, müssen die Batterien nach maximal 4 Betriebsjahren Wir danken Ihnen, dass Sie ein V-TAC ausgesucht und gekauft haben. V-TAC wird Ihnen die besten Dienste • Schneiden Sie eine geeignete Öffnung in die Decke gemäß den Ausschnittdetails in Abb. 1, um sicherzustellen, ausgetauscht werden.
  • Page 6 MANTENIMIENTO Le agradecemos que ha elegido y adquirido la V-TAC. V-TAC le servirá del mejor modo posible. Pedimos que • Corte una abertura adecuada en el techo según los detalles de corte en la Fig. 1, asegurándose de que no Si la iluminación ya no puede proporcionar el período nominal de funcionamiento de emergencia, las baterías...
  • Page 7 Lorsque le luminaire ne répond plus au fonctionnement de secours nominal, les piles doivent être remplacées Merci d’avoir choisi et acheté un produit à V-TAC. V-TAC vous offrira le meilleur. Veuillez lire attentivement ces • Découpez une ouverture appropriée dans le plafond conformément aux détails de la découpe de la Fig. 1 en après un maximum de 4 ans de service.
  • Page 8 • Osigurajte napajanje do željene točke gdje će te ršiti montažu. Hvala vam, što ste odabrali i kupili tvrtke Vi-Tek (V-TAC). Vi-Tek (V-TAC) će vam poslužiti na najbolji mogući • Izrežite odgovarajući otvor na stropu prema detaljima izrezivanja na slici 1, osiguravajući da ne krši električne Ako rasvjetno tijelo više ne može pružiti nominalno razdoblje rada u nuždi, baterije se moraju zamijeniti nakon...
  • Page 9 Se a luminária não puder mais fornecer o período nominal de operação de emergência, as baterias devem ser Agradecemos que escolheu e adquiriu o produto da V-TAC. A V-TAC irá servir-lhe da melhor maneira possível. • Corte uma abertura adequada no teto conforme os detalhes do recorte na Fig. 1 garantindo que não interfira substituídas após um máximo de 4 anos de operação.
  • Page 10 Po maksymalnie 4 latach eksploatacji lub jeśli oprawa oświetleniowa nie zapewnia już nominalnego okresu pracy Dziękujemy za wybór i zakup produktu V-TAC. V-TAC będzie Ci służył najlepiej. Prosze przeczytać tę instrukcje • Wytnij w suficie odpowiedni otwór zgodnie z wycięciem na rys. 1, upewniając się, że nie narusza on kabli awaryjnej akumulatory należy wymienić.
  • Page 11 ΤΕΧΝΙΚΗ ΣΥΝΤΗΡΗΣΗ • Παρέχετε τροφοδοσία στο επιθυμητό σημείο εγκατάστασης. Σας ευχαριστούμε για το ότι επιλέξατε και αγοράσατε το προϊόν της Βι-ΤΑΚ(V-TAC). Η Βι-ΤΑΚ (V-TAC) θα σας Εάν το φωτιστικό δεν μπορεί πλέον να παρέχει την ονομαστική περίοδο λειτουργίας έκτακτης ανάγκης, οι...
  • Page 12 4 ani. Vă mulţumim că aţi ales şi v-aţi cumpărat acest produs de V-TAC. V-TAC vă va fi de un mare folos, utilizându-l • Asiguraţi alimentarea până la punctul de instare dorit.
  • Page 13 ÚVOD A ZÁRUKA • Zajistěte napájení požadovaného místa instalace Děkujeme, že jste si vybrali a koupili výrobek firmy V-TEK (V-TAC). V-TEK (V-TAC) vám nabízí ty nejlepší ÚDRŽBA • Ve stropě vyřízněte vhodný otvor podle podrobností výřezu na obr. 1, aby nedošlo k jeho narušení elek- výrobky.