E) POWER LINE WIRING
E) POWER LINE WIRING
E) POWER LINE WIRING
E) POWER LINE WIRING
E) POWER LINE WIRING
N, L2
9
POWER SUPPLY
100 to 240 Vac
24 Vac/Vdc
10
R (S,T), L1
Fig. 14 POWER LINE WIRING
NOTE
NOTE
NOTE
NOTE
NOTE:
1) Before connecting the power line, check that
the voltage is correct (see Model Number).
2) For supply connections use 16 AWG or larger
wires rated for at least 75 °C (167 °F).
3) Use copper conductors only.
4) Do not run input wires with power cables.
5) Polarity does not matter for 24 Vdc wiring.
6) The power supply input is NOT
Please provide it externally.
Power supply
24 V AC/DC
100/240 V AC
When fuse is damaged, it is advisable to verify
the power supply circuit, so that it is necessary to
send back the instrument to your supplier.
7) Safety requirements for permanently
connected equipment:
- Include a switch or circuit-breaker in the
installation.
- Place the switch in close proximity to the
equipment and within easy reach of the
operator.
- Mark the switch as the disconnecting device
for the equipment.
NOT
NOT
NOT fuse protected.
NOT
Type
Current
Voltage
T
500 mA
250 V
T
125 mA
250 V
NOTE
NOTE
NOTE: A single switch or circuit-breaker can
NOTE
NOTE
drive more than one instrument.
8) When the NEUTRAL line is present, connect it
to terminal 9.
9) To avoid shock and possible instrument
damage, connect power last.