Overview of the LED status:
Status
Indication
Start up
The red LED flashes On for two seconds and Off for
two seconds. The startup time is around 60 seconds
after power supply is connected.
Power on
The blue LED flashes On for two seconds and Off for
two seconds. The power supply is connected, but
there is no program in the detector.
KNX program-
The red LED remains illuminated until the addressing
ming mode
is selected.
Test mode
The blue LED will flash On for 0.2 seconds when
sector A
activity is detected in sector A.
Test mode
The green LED will flash On for 0.2 seconds when
sector B
activity is detected in sector B.
Test mode
The red LED will flash On for 0.2 seconds when activ-
sector C
ity is detected in sector C.
IR-remote
Each time the detector receives a correct signal from
control
the IR remote control, the detector will acknowledge
with a flash from the green LED lasting 0.3 seconds.
Upward
The red LED flashes On for 0.2 seconds and Off for
adjustment
0.2 seconds the number of times corresponding to
the number of steps by which the current value has
been increased relative to the setting configured in
the ETS software.
Downward
The blue LED flashes On for 0.2 seconds and Off for
adjustment
0.2 seconds the number of times corresponding to
the number of steps by which the current value has
been decreased relative to the setting configured in
the ETS software.
Unlock
The green LED flashes On for 0.3 seconds and Off for
0.2 seconds. This is repeated four times, after which
the detector will be unlocked and ready for configura-
tion via the IR remote control.
Lock
The green LED flashes On for 0.3 seconds and Off for
0.2 seconds. This is repeated twice. The detector is
locked and the most recently programmed changes
are saved.
Function
If you activate a function requiring the detector to be
locked
unlocked for settings configurations and this is not
the case, this is signalled by a flash from the red LED
lasting 0.3 seconds.
Error: Range
The red LED flashes twice if the configuration is out of
range. This can be either time or the lux setting.
Calibration
The red LED flashes On for two seconds and Off for
three seconds while the fittings are warming up as
part of auto calibration. This sequence is repeated for
two minutes.