Ariston RVS 63 Instructions De Montage page 39

Table des Matières

Publicité

MENU
DHW
Engineer
(Storage cylinder)
DHW
Engineer
(Storage cylinder)
Engineer
Cascade
Engineer
DHW storage
Engineer
Confi guration
PARAMETER
DESCRIPTION
Legionella funct time
1644
(function start time)
Legionella funct setpoint
1645
(temperature at end of anti-Legionnaire's
disease function)
Legionella funct duration
1646
(maximum Legionella funct duration)
Legionella funct circ pump
1647
(DHW recirculation pump activation
during function)
Time program release
(this parameter sets the DHW storage
cylinder management according to the
following selection:
1620
- 24h/day > always active
- Time programs HCs > follows the
heating time program
- Time program 4/DHW > dedicated time
schedule)
Charging priority
(Manages the Storage Cylinder priority
according to the following selection:
- Absolute > heating deactivated
- Shifting > when the generator's heat
output is no longer suffi cient, the mixed
circuit and direct circuit are switched
off until storage cylinder fi lling is
1630
completed
- None > storage cylinder simultaneous
to heating
- MC shifting, PC absolute. > the direct
circuits remain blocked until fi lling of
the DHW storage cylinder is completed.
When the generator's heat output is no
longer suffi cient, the mixing circuits are
also limited.)
Auto kilde.sekv.omkobling
(switching time of the boiler ignition sequence.
By setting the "---" the ignition sequence
3540
is fi xed.
The fi rst boiler of the sequence is settable
through parameter 2544)
Leading source
3544
(fi rst boiler of the fi xed sequence see
parameter 3540)
Flow setpoint boost
Manifold temperature increase during
heating up of the storage cylinder.
The system takes as reference the set
storage cylinder temperature that must be
5020
added to the present parameter
E.g.: Nominal set-point (par. 1610) = 60°C
(par. 5020) = 15°C
60 + 15 = 75°C
This means that during heating up of the
storage cylinder the manifold operates at 75°C
Reset to default parameters
6205
(restores the parameters to the default
settings)
RANGE
55-95°C
--- ÷ 360nw
On - Off
- 24h/day
- Time programs
HCs
Time program 4/DHWl
- Time program
4/DHW
- Absolute
- Shifting
- None
MC shifting, PC absolute
- MC shifting, PC
absolute
10-990h
- Source 1
- Source 16
0 - 30°C
yes - no
GB
VALUE
--:--
65°C
10 min
On
500h
16°C
no
39

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

3590468

Table des Matières