WHITE-RODGERS
Operator: Save these instructions for future use!
FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE
INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL
INJURY AND/OR PROPERTY DAMAGE.
These "Level-Temp" controls have been designed to
operate with a White-Rodgers low-voltage electric heat
thermostat to provide a system for controlling electric
warm air heaters and electric radiant heating devices
such as duct heaters, wall heaters, baseboards, floor and
ceiling cable heaters.
When required, two or more Level-Temp Silent Opera-
tors can be operated by one two-wire low voltage thermo-
stat.
The operator has been carefully adjusted. No attempt
should be made to adjust it after it leaves the factory.
If in doubt about whether your wiring is millivolt, line, or
low voltage, have it inspected by a qualified heating and
air conditioning contractor, electrician, or someone famil-
iar with basic electricity and wiring.
Do not exceed the specification ratings.
All wiring must conform to local and national electrical
codes and ordinances.
This control is a precision instrument, and should be
handled carefully. Rough handling or distorting compo-
nents could cause the control to malfunction.
ELECTRICAL DATA
Switch Action: Single-Pole, Single-Throw, normally open
Thermal: Average time delay – 45 seconds
Ambient Temp.: -20° to 140°F (-24° to 60°C)
TYPE
NUMBER
VOLTAGE /FREQUENCY
24A01G-3
240VAC, 60 Hz
24A01Z-10
347VAC, 60 Hz
24A01Z-11
600VAC, 60 Hz
24A05A-1
120VAC, 60 Hz
24A05E-1
208VAC, 60 Hz
24A05Z-1
277VAC, 60 Hz
Mounting: 1/2" conduit hub or mounting tabs with several break-offs for 2, 3 or 4 hole mounting
WHITE-RODGERS DIVISION
EMERSON ELECTRIC CO.
9797 REAVIS RD., ST. LOUIS, MO. 63123
(314) 577-1300,
9999 HWY. 48, MARKHAM, ONT. L3P 3J3
(905) 475-4653, FAX (905) 475-4625
INPUT
THERMOSTAT
CURRENT
0.2A
0.2A
0.2A
0.2A
0.2A
0.2A
FAX (314) 577-1517
TYPE 24A01 / 24A05
"SLIMLINE" LEVEL-TEMP
SILENT OPERATOR
INSTALLATION INSTRUCTIONS
To prevent electrical shock and/or equipment
damage, disconnect electric power to system, at
main fuse or circuit breaker box, until installation
is complete.
Do not use on circuits exceeding specified
voltages. Higher voltages will damage control
and could cause shock or fire hazard.
Room Thermostat:
Set adjustable heat anticipator at 0.2 Amps. For fixed
anticipation thermostats, use 0.15 to 0.25 Amp. heater.
A.C.
RESISTIVE
NON-INDUCTIVE
25A, 6000W, 240V
17A, 5900W, 347V
12A, 7200W, 600V
25A, 3000W, 120V
25A, 5200W, 208V
22A, 6000W, 277V
Printed in U.S.A.
(Normally Open)
DESCRIPTION
PRECAUTIONS
CAUTION
WARNING
SPECIFICATIONS
A.C. MOTOR INDUCTIVE
FULL LOAD
LOCKED ROTOR
12A, 240V
72A, 240V
16A, 120V
96A, 120V
12A, 208V
72A, 208V
PART NO. 37-4701C
Replaces 37-4701B
0023

Publicité

loading

Sommaire des Matières pour Emerson White-Rodgers 24A01

  • Page 1 0.2A 22A, 6000W, 277V Mounting: 1/2" conduit hub or mounting tabs with several break-offs for 2, 3 or 4 hole mounting WHITE-RODGERS DIVISION EMERSON ELECTRIC CO. PART NO. 37-4701C 9797 REAVIS RD., ST. LOUIS, MO. 63123 (314) 577-1300, FAX (314) 577-1517 Replaces 37-4701B Printed in U.S.A.
  • Page 2 OPERATION WIRING Line Voltage Basic Silent Operator components are a line-to-low volt- LINE Line Voltage Field age transformer, a low voltage bimetal heater, an ambi- Low Voltage ent compensating bimetal, and a normally open SPST TRANSFORMER line voltage snap-action switch. In operation, a circuit is completed through the bimetal WHITE heater as the low voltage room thermostat closes its...
  • Page 3 WIRING CONT. All wiring should be done in accordance with local and national electrical codes and ordinances. If the manufacturer of the heating equipment has in- HEATING cluded a wiring diagram, follow such recommendations. ELEMENT If none is available, these diagrams show suggested methods of attaching and wiring the “Level-Temp”...
  • Page 4 WIRING CONT. All wiring should be done in accordance with local and national electrical codes and ordinances. SILENT OPERATOR # 1 TO LOW VOLTAGE ROOM THERMOSTAT YELLOW MAKE L2 “HOT” WHITE BLACK ON 120V MODELS BLUE NOTE LOAD # 1 Use thermostat with a .2A fixed heater, or set adjustable heater in thermostat at .2A.
  • Page 5 22 A, 6000 W, 277 V Installation : Raccord de conduite de 1/2" ou pattes de montage détachables permettant le montage à 2, 3 ou 4 trous. WHITE-RODGERS DIVISION EMERSON ELECTRIC CO. PIÈCE NO 37-4701C 9797 REAVIS RD., ST. LOUIS, MO. 63123 (314) 577-1300, Télécopieur (314) 577-1517...
  • Page 6 FONCTIONNEMENT CÂBLAGE Tension du réseau Les composantes de base du relais silencieux sont un Champ à la tension du réseau transformateur tension de réseau à basse tension, un élément RÉSEAU chauffant à basse tension, un bilame compensateur à tempéra- Basse tension ture ambiante et un commutateur unipolaire unidirectionnel à...
  • Page 7 CÂBLAGE (suite) Tout le câblage doit être conforme aux codes et règlements locaux et nationaux qui régissent les installations électriques. ÉLÉMENT Si un schéma de câblage est fourni avec l’équipement de CHAUFFANT chauffage, alors veuillez vous y référer. Si aucun schéma n’est fourni, ceux qui figurent ici présentent plusieurs façons de câbler le relais «...
  • Page 8 CÂBLAGE (suite) Tout le câblage doit être conforme aux codes et règlements locaux et nationaux qui régissent les installations électriques. RELAIS SILENCIEUX # 1 ROUGE VERS LE THERMOSTAT D’AMBIANCE À BASSE TENSION JAUNE BLANC MODÈLES DE 120V : NOIR METTRE L2 BLEU SOUS TENSION NOTE...

Ce manuel est également adapté pour:

White-rodgers 24a05