ELEVATION™ X 42 DIRECT VENT GAS FIREPLACE
Product information provided is not complete and is subject to change without notice. Please consult the installation manual for
the most up to date installation information.
Wall Penetration
1" [25mm] minimum all sides for vertical venting sections.
When passing through a ceiling, use firestop
W500-0028 (not supplied).
Non-combustible
material
12"
[305mm]
72"
(182.8cm)
min.
Framing
Flush Finish Framing
72"
(182.8cm)
min.
Wolf Steel Ltd., 24 Napoleon Rd., Barrie, ON L4M 0G8 Canada •
Combustible
Non-combustible
Brick
0" [0mm] if non-combustible
finishing material is used
such as brick and stone.
3"
[76mm]
to top
4"
min.
Insulated
sleeve
2"
[51mm] to
sides / bottom
Firestop
10 1/4"
assembly
1" [25mm]
47 3/4"
45 3/4"
note:
Vent Sections
When passing through a wall, use
fi restop spacer W010-1800 (supplied).
When passing through a ceiling,
use fi restop spacer W500-0028 (not
supplied).
Horizontal vent sections: A minimum
clearance of 3" (76mm) on the top of
63"
the vent to combustibles and 2" (51mm)
plus rise
on the sides and bottom of the vent to
combustibles is required.
Vertical vent sections: A minimum
clearance of 1" (25mm) all around the
vent pipe on all vertical runs to combus-
tibles is required.
Recessed Finish Framing
72"
(182.8cm)
min.
Recessed
volume must
be added to
the overall size
of the
enclosure.
* Recess frame can be "backed" with 3/4" ply to support TV mounting hardware.
1(866)820-8686
Max. 5 1/2"*
47 3/4"
45 3/4"
W415-2777 / A / 10.07.19
•