Télécharger Imprimer la page

Johnson Controls VA9320-AUA Serie Mode D'emploi page 11

Publicité

VA9320-AUA-x / VA9320-HGA-x / VA9335-AUA-x / VA9335-HGA-x
Technical Specifications
Product Code
• Code produit • Produktcode • Codice prodotto • Código de
producto • Productcode • Produktkod • Kód produktu • Kod
produktu • Код продукта • Código do produto • 产品代码
• 製品コード
Control Type
• Type de commande • Steuerungsart • Tipo di comando
• Tipo de control • Besturingstype • Kontrolltyp • Typ řízení
• Typ sterowania • Тип управления • Tipo de controlo • 控制
类型 • 制御タイプ
Power
Transformer
Input
• Entrée • Eingang • Ingresso • Entrada • Ingang • Ingång
• Vstup • Wejście • Вход • Entrada • 输入 • 入力
Impedance
• Impédance • Impedanz • Impedenza • Impedancia
• Impedantie • Impedans • Impedance • Impedancja
• Импеданс • Impedância • 阻抗 • インピーダンス
Feedback
• Rétroaction • Rückmeldung • Ritorno • Realimentación
• Feedback • Feedback • Zpětná vazba • Sprzężenie zwrotne
• Обратная связь • Feedback • 反馈 • フィードバック
Torque
M
Rotation Range
Rotation Time
Compliance
VA9320-HGA-1
VA9320-HGA-2
VA9320-HGA-3
On/Off, Floating
Proportional
24 V ±20%, 50/60 Hz, 5.7 VA
24 VDC ±10%, 2.1 W
0(2)...10 VDC,
0(4)...20 mA with field
furnished 500 ohm
24 VAC ±20%
24 VDC ±10%
Offset: 0...10 VDC
Span: 2...10 VDC
4.7k ohm
100k ohm
0(2)...10 VDC
20 Nm (180 lb. in)
Mechanically Limited to 35...95° +/- 3° in 5° increments
90 s
United States: UL Listed, CCN XAPX, File E27734; to UL 60730-1: Automatic Electrical Controls for
Household and Similar Use, Part 1; and UL 60730-2-14: Part 2, Particular Requirements for Electric
Actuators. Plenum Rated (UL 2043). Suitable for use in Other Environmental Air Space (Plenum) in
accordance with section 300.22 (c) of the National Electrical Code.
Canada: UL Listed, CCN XAPX7, File E27734; to CAN/CSA E60730-1:02: Automatic Electrical
Controls for Household and Similar Use, Part 1; and CAN/CSA-E60730-2-14, Particular
Requirements for Electric Actuators.
Europe: CE Mark
Johnson Controls declares that these products are in compliance with the essential requirements
and other relevant provisions of the EMC Directive and Low Voltage Directive.
Australia and New Zealand: RCM Mark, Australia/NZ Emissions Compliant
11
VA9335-HGA-1
VA9335-HGA-2
VA9335-HGA-3
On/Off, Floating
24 V ±20%, 50/60 Hz, 6.1 VA
24 VDC ±10%, 2.1 W
≥7 VA
24 VAC ±20%
resistor
24 VDC ±10%
4.7k ohm
35 Nm (310 lb. in)
Proportional
0(2)...10 VDC,
0(4)...20 mA with field
furnished 500 ohm
resistor
Offset: 0...10 VDC
Span: 2...10 VDC
100k ohm
0(2)...10 VDC
150 s
34-00636-02510 Rev. –

Publicité

loading

Ce manuel est également adapté pour:

Va9320-hga serieVa9335-aua serieVa9335-hga serie