VALPES VSX.P5 Serie Documentation Technique Mise En Service page 22

Actionneur electrique
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

VALPES company - 89, rue de Etangs - 38430 Moirans - France, gives evidence that his 1/4 turn electric actuators
are produced, in compliance with the ATEX 94/9/CE directive intended to be used in explosive atmosphere, are in compliance
with the certificate of exam type LCIE 06 ATEX 6006X (available on demand) and have a production quality notification
ATEX Q8010.
The conditions to use of our actuators VRX and VSX are defined with their ATEX classification :
II 2 GD
Ex d IIB T6 - tD A21 IP67 T80°C
II :
Group II, devices intended to be used in places, others than mines or fire-damp installations
susceptible to be put in danger by explosive atmospheres.
2 :
Category 2, likely, but coincidental presence of explosive atmospheres.
GD :
Presence of Gas or vapors and/or dust.
EX:
Electric material foreseen for explosive atmospheres.
d :
Protection by explosion proof housing.
IIB :
Places where explosive hydrocarbon atmosphere is established (constituted)
(Ethylene, nitrogenous products, oxygenated, halogens).
T5 :
Maximal surface Temperature 100°C. Ambient temperature of use : -20°C in +70°C
T6 :
Maximal surface Temperature 85°C. Ambient temperature of use : -20°C in +70°C.
tD A21 IP67 T80°C : IP67 protection assured, maximal surface temperature for dust atmospheres 80°C.
tD A21 IP67 T95°C : IP67 protection assured, maximal surface temperature for dust atmospheres 95°C
The devices are in comliance with the following norms :
EN 60079-0 (2004) and EN 60079-1 (2004) : Electric Material for exploding gaseous atmospheres (gas-filled)
EN 61241-0 (2006) and EN 61241-1 (2004) : Electric Material for usage in the presence of de poussières flammable dusts
The electric connecting has to respect current ATEX recommendations (BE3 conditions of NF C-15100 and EN 60079-14).
The notified body in charge of the production quality surveillance is LCIE (N° |0081) :
LCIE - 33, avenue du Général Leclerc - BP 8 - 92266 Fontenay-aux-Roses cedex - France
The VALPES company, as the manufacturer declares herewith, that the above mentioned electric VALPES part-turn actuators are
in compliance with the following directives :
- Directive on Electromagnetic Compatibility (EMC)(2004/108/CE)
EN 61000-6-2 (2001) : Immunity
EN 61000-6-4 (2001) : Emissions
- Low-voltage Equipment Directive (2006/95/CE)
EN 61010-1 (2001)
- Machinery Directive (2006/42/CE)
VALPES part-turn actuators covered by this Declaration must not be put into service until the entire machine, into which they are
incorporated, has been declared in conformity with the provisions of the directive.
VALPES Valve Control System
ZI CENTR'ALP - 89 rue des Étangs - F 38430 MOIRANS
Tél. : (+33) 04-76-35-06-06
Fax : (+33) 04-76-35-14-34
E-mail : info@valpes.com / Site web : www.valpes.com
We declare under our responsibility that the products noted have been designed and manufactured in accordance with requirements of the directive. Mounting and
connecting instructions defined in catalogues and technical data sheets must be adhered to by the user. This declaration does not include any guarantee or certain
characteristics.
DSBA2803 rév.24/04/2008
EC
Declaration of conformity
VRX25 - VRX45 - VRX75
VSX100 - VSX150 - VSX300
For 400V actuators and actuators with EBS.24 :
II 2 GD Ex d IIB T5 - tD A21 IP67 T95°C
Moirans, le 24/04/2008
J. Serres, ATEX responsible
DSBA1509 rév.24/04/2008
LCIE_04-