Aut Mode - ITALFARAD PFC96evo Manuel Opérationnel

Régulateur automatique du facteur de puissance
Masquer les pouces Voir aussi pour PFC96evo:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

 In automatic mode, the controller calculates the optimum configuration of capacitor steps
in order to reach the set cosø.
 The selection criteria takes into account many variables such as: the power of each step, the
number of operations, the total time of use, the reconnection time, etc.
 The controller displays the imminent connection or disconnection of the steps with the
flashing of their identification number (left). The flashing can last in cases in which the
insertion of a step is not possible due to the reconnection time (discharge time of the
capacitor).
 The device initiates automatic corrections when there is an average reactive power request
(delta-kvar) higher than 50% of the smallest step, and the measured cosø is different from
the setpoint.
 The PFC96evo controller provides a set of measurements displayed on the alphanumeric
display, in conjunction with the current cosø that is always displayed on the main display.
 Press the
key to scroll through the measures in rotation.
 After 30 seconds without pressing any buttons, the display automatically returns to the
default measurement defined by P.47.
 If P.47 is set on the ROT, then the measures rotate automatically every 5 seconds.
 At the bottom of the list of measures it is possible to set the setpoint of the cosø, acting on
the same value set with P.19.
 Below is a table with the measurements displayed.
Tel.+39 051 6618311 Fax +39 051 6605594 E-mail: italfarad@italfarad.com Web: www.italfarad.com

AUT mode

Measurements
ITALFARAD S.p.A. via IV novembre n.1 Minerbio Bo Italy
E
N
39

Publicité

Table des Matières
loading

Table des Matières