Installation Instructions - Extreme High Bay Installation Manual
Power Quality
High frequency voltage shall be below -40dB or .01V between 3KHz and 100KHz.
High frequency current shall be below -50dB or .019A between 3KHz and 100KHz.
If you require assistance in checking your power system or designing or implementing solutions, contact Cooper Lighting
Solutions' Electrical Engineering Services and Systems. Find more information at www.cooperlighting.com.
Failure to ensure power quality requirements shall void warranty.
INSTALLATION INSTRUCTIONS
Refer to photometric drawings or project installation instructions for luminaire locations and mounting configuration.
Luminaire housings can become very hot. Luminaire must be mounted clear of any flammable or temperature sensitive
●
●
objects.
Luminaire performance will be decreased if placed directly next to a solid object that does not allow air circulation through
●
●
the fins of the heat sink.
It is the responsibility of the installer to verify that all proposed mounting structures are certified to support the weight
●
●
of the luminaires and meet all applicable codes and regulations. FAILURE TO FOLLOW THIS WARNING MAY LEAD TO
DEATH, SEVERE INJURY, OR PROPERTY DAMAGE.
Do not suspend any luminaire by electrical or control wires, as these will not support the weight of the fixture, resulting
●
●
in the potential for the fixture to fall and cause damage or injury. FAILURE TO FOLLOW THIS WARNING MAY LEAD TO
DEATH, SEVERE INJURY, OR PROPERTY DAMAGE.
The fixture must be powered off during the installation process. FAILURE TO FOLLOW THIS WARNING MAY LEAD TO
●
●
LUMINAIRE INTERNAL DAMAGE AND FAILURE.
MOUNTING OPTION 1 - PENDANT MOUNTING
1.
Remove the two junction box screws using a 3/16" hex Allen wrench (Figure 2).
Figure 2.
4
COOPER LIGHTING SOLUTIONS
WARNING
Power wire cord grip
IB507004EN
Installation instructions
Control Wire Access
(Optional)
Set Screw
3/4" NPS for Pendant
or Hook Mount
Flush Mount
Mounting Holes (5X)
Junction Box Screws (2X)