unit has a jumper between
pins 1-2 or that it is properly
wired to an Emergency Power-
Off circuit (normally closed).
3. Make sure the breaker supplying
power to the UPS is closed, and
close the input breaker on the
rear of the UPS.
4. If necessary, use the LCD
display or a connected
computer to make any required
settings. (Refer to the User
Guide for configuration set up.)
5. Close all output breakers on the
rear of the UPS (or in an external
panel board, if used).
6. If external battery cabinets are
included, close the breakers on
the rear of each cabinet.
7. Power-on the UPS using the
Operation and Display Panel
(see the illustration on the
previous page) by pressing and
holding the power button until
the confirmation dialog appears.
Use the Up/Down arrows to
select "YES", then press Enter.
NOTE: During operation, the UPS
may sound an alarm as the output
receptacles are powered. You may
press the Esc button for 2 seconds
to silence the audible alarm.