1 - mecHanIcal InstallatIon
Fix the uninterrupted power supply in its place.
2 - electRIcal InstallatIon
Connect the mains 230VAC (fig. 2).
The mains supply for this device must include a neutral phase circuit
breaker of maximum 16A C curve, rapidly accessible upstream from the
supply.
All cables must be attached to the frame of the cabinet before being
connected to the various terminals strips, to prevent any pulling on these
terminal strips. In addition, the wires of each terminal strips must be
attached to each other to maintain the various isolations if an initial fault
occurs.
Connect the 24VDC output (fig. 3).
Connect if needed the 2 dry contacts indicating mains failure and low
battery.
The triggering of the
low battery contact can
be adjusted with the
potentiometer 5 (fig. 3).
Connect the battery before closing the Sigma UPS and switching it on
(fig. 4).
When the installation (24V) includes several Sigma UPS the earth poles of
the sigma UPS should be interconnected.
1 – Green LED indicating that batteries are charging.
2 – Red LED indicating that battery connection is inverted.
3 – Green LED indicating power presence.
4 – Red LED indicating that the system is working on batteries.
5 – Low battery threshold adjustment (preset in factory)
3 - tecHnIcal FeatuRes
► AC/DC switched-mode power supply.
► Input: 85 – 264 VAC.
► Output: 28VDC regulated at 5A permanentlyt.
► Battery reserve: 2 rechargeable sealed lead-acid batteries 7.2Ah, 12V.
► Fuses Protection.
► Mains LED indicator.
► Battery LED indicator (power outage).
► Battery full charge LED indicator.
► Normally-closed contact for power outage indication.
► Normally-closed contact for UPS failure or low battery (21V) indication.
► Dimensions of wall version: H294 x L225 x D122 mm.
► Dimensions of rack version: H132 x L483 x D277 mm.
► Operating temperature: 0 to +50°C.
► Weight of wall version: 8 Kg.
► Weight of rack version: 9 Kg.
► Protection index: IP30.
Applicable norms :
► NF EN 61000-3-2: EMC directive.
► NF EN 61000-3-3: EMC directive
73/23/CEE/89/336: low voltage.
► Constant current discharge from 7.2Ah batteries at 25°C. Charge time: 24h.
1 Ampère
2 A
5h00
3h15
Installation instructions
uninterrupted power supply sIgma uPs
Check the product for shipping damage on reception for any reservations to the carrier
Medium 22V
Minimum 21V
Maximum 23V
3 A
4 A
1h30
1h15
FIg. 1 :
Rack version
483
443
FIg. 2 :
L N Earth
Power supply
1
FIg. 3 :
5
- + 24VDC
Output
FIg. 4 :
5 A
1h00
Wall version
122
Low battery threshold
adjustment (preset in
2
3
Mains failure contact
Low battery contact
Secondary fuse
BP1 49340 TRÉMENTINES
FRANCE
Tél. 02 41 71 72 00
Fax. 02 41 71 72 01
www.bodet.com
.
225 mm
factory)
4