Time 2
Setting the orientation lighting delay.
Setting range (factory setting 1 min.).
Min. = Orientation lighting – activated, infi nite delay.
0 = Orientation lighting – deactivated 0 min.
1-60 = Orientation lighting – activated, delay 1-60 mins.
For example setting the orientation lighting delay:
Factory settings: 1 minute = Orientation lighting is activated,
delay 1 minute
Press button
: Setting = 0, orientation lighting is deactivated.
Time2
-1
Press button again
: Setting = min., orientation lighting is
Time2
-1
activated, infi nite delay.
Learn in
Commissioning the sensor, setting of the sensor with calibration
(sweep).
Read more in the manual for 41-351 under Commissioning item:
"Via the remote control unit, type 41-922 (accessory), individual
setpoint and calibration zone 1".
Adj.
Not used for this product.
Fade
Not used for this product.
Level 1 (Hysteresis)
Setting the positive hysteresis for setpoint.
Setting range 10-100% (factory setting 20%).
10% intervals per press.
Level 2 (Orientation lighting level)
Setting the orientation lighting level.
Setting range 5-100% (factory setting 5%).
5% intervals per press.
Lux values under the buttons
The lux values are reference values used when commissioning
the sensor.
Read more in the manual for 41-351 under Commissioning item:
"Via the remote control unit, type 41-922 (accessory), individual
setpoint and calibration zone 1".
Servodan A/S | Tel +45 7442 4726 | Fax + 45 7442 4035 | info@servodan.dk | www.servodan.com
Glossary 41-351
App. Man:
Application manual, manual on and off via pushbutton switch,
automatic off via presence detector, or light level.
App. Auto:
Application automatic, automatic on and off via presence
detector, light level dependent.
Setpoint:
Desired light level (lux) at table height.
Set using Lux potentiometer or Set 1 on IR Remote.
Off delay:
Cut-off time before the presence detector switches off the light.
Set using Time potentiometer or Time 1 on IR Remote.
Orientation lighting:
If the PIR does not register the activity, off delay has elapsed
and there is insuffi cient daylight, the lighting is dimmed to the
set level "Level 2"; after the set time "Time 2", the lighting is
switched off completely.
Factory settings for 41-351:
Application ................................App. Man
Setpoint .....................................300 lux
Setpoint hysteresis ....................20%
Orientation lighting level ............5%
Orientation lighting time ............1 min.
Off delay (Time) .........................10 mins
Setting Lux and Time ................Via IR remote control