Time 2
Setting the orientation lighting delay.
Setting range (factory setting 1 min.).
Min. = Orientation lighting – activated, infi nite delay.
0 = Orientation lighting – deactivated 0 min.
1-60 = Orientation lighting – activated, delay 1-60 mins.
For example setting the orientation lighting delay:
Factory settings: 1 minute = Orientation lighting is activated,
delay 1 minute
Press button
: Setting = 0, orientation lighting is deactivated.
Time2
-1
Press button again
: Setting = min., orientation lighting is
Time2
-1
activated, infi nite delay.
Learn in
Commissioning the sensor, setting of the sensor with calibration
(sweep).
Read more in the manual for 41-350 under Commissioning item:
"Via the remote control, type 41-922 (accessory), individual
setpoint and calibration zone 1 and 2".
Adj.
Not used for this product.
Fade
Setting the DALI coil fade time.
Fade time is a part of the DALI specifi cation.
Setting range 0-15 (factory setting 0).
However, we recommend that this is kept at 0 as there can
otherwise be perceived to be a delay from pressing the door
button until there is a noticeable change in the lighting.
Level 1 (Hysteresis)
Setting the positive hysteresis for setpoint.
Setting range 10-100% (factory setting 20%).
10% intervals per press.
Level 2 (Orientation lighting level)
Setting the orientation lighting level.
Setting range 5-100% (factory setting 5%).
5% intervals per press.
Lux values under the buttons
The lux values are reference values used when commissioning
the sensor.
Read more in the manual for 41-350 under Commissioning item:
"Via the remote control, type 41-922 (accessory), individual
setpoint and calibration zone 1 and 2".
Glossary 41-350
App. Man:
Application manual, manual on and off via pushbutton switch,
automatic off via presence detector, or light level.
App. Auto:
Application automatic, automatic on and off via presence
detector, light level dependent.
Setpoint (zone 1):
Desired light level (lux) at table height in zone 1.
Set using Lux potentiometer or Set 1 on IR Remote.
Servodan A/S | Tel +45 7442 4726 | Fax + 45 7442 4035 | info@servodan.dk | www.servodan.com
Setpoint (zone 2):
Desired light level (lux) at table height in zone 2.
Set using IR remote control Set 2.
Off delay:
Cut-off time before the presence detector switches off the light.
Set using Time potentiometer or Time 1 on IR Remote.
Fade time:
The ramp time for the light fi ttings.
Fade factor must be increased if the light fi ttings "fl icker" when
adjustments are made.
Orientation lighting:
If the sensor does not register the activity, off delay has elapsed
and there is insuffi cient daylight, the lighting is dimmed to the
set level "Level 2"; after the set time "Time 2", the lighting is
switched off completely.
Factory settings for 41-350:
Application ................................App. Man
Setpoint zone 1 .........................300 lux
Setpoint hysteresis ....................20%
Orientation lighting level ............5%
Orientation lighting time ............1 min.
Factor zone 2 ............................300 lux
Off delay (Time) .........................10 mins
Fade factor DALI .......................0 (optional 0-15 in relation to DALI
standard)
Setting Lux and Time ................Via IR remote control
Output bus ................................DALI
Setting 41-351
When the remote is pressed and the green LED does not
acknowledge, even if the sensor is in edit mode, you have
already reached the minimum or maximum of the setting range.
Ref.
Used for changing the desired lux setpoint (without performing
calibration/sweep).
Read more in the manual for 41-351 under Commissioning item:
"Via the remote control unit, type 41-922 (accessory), individual
setpoint and calibration zone 1".
Set 1 (Setpoint)
Setting the required lighting level.
When setting the setpoint, the lighting is switched on to show
the set lighting level.
Set 2
Not used for this product.
Time 1
Setting off delay (cut-out delay).
Setting range 1-60 min. (factory setting 10 min.).