Configuration and function check REV24RF..
DE
1
Configuration
EN
1.1
DIP switches
FR
ON /
Sensor calibration on
See 1.1.1
IT
Sensor calibration off
Setpoint limitation 16...35 °C
1.1.2
Setpoint limitation 3...35 °C
NL
Temperature display °F
1.1.3
Temperature display °C
ES
PID self-learning
PT
PID 6
1.1.4
PID12
CS
2-Point
HU
1.1.9
When changing one or several DIP switch positions, a DIP switch reset must be made by pressing the DIP switch reset button (also refer to Fig.
PL
8). Otherwise, the previous settings will be maintained!
SV
1.1.1 Sensor calibration: DIP switch 1
Set the DIP switch to ON and press the DIP switch reset button:
FI
The display shows CAL. The room temperature currently acquired blinks.
Press
or
to make a recalibration of max. ± 5 °C. To save the entry,
set the DIP switch to OFF and press the DIP switch reset button (also refer to
DA
Fig.
).
1.1.2 Setpoint limitation: DIP switch 2
TR
DIP switch ON:
Setpoint limitation 16...35 °C
DIP switch OFF: Setpoint limitation 3...35 °C
EL
Save the entry by pressing the DIP switch reset button.
1.1.3 Temperature display in °C or °F:
RO
DIP switch 3
DIP switch ON:
Temperature display in °F
DIP switch OFF: Temperature display in °C
Save the entry by pressing the DIP switch reset button (also refer to Fig.
1.1.4 Control action: DIP switches 4 and 5
DIP switch 4 ON and 5 ON:
Adaptive control for all types of application.
DIP switch 4 ON and 5 OFF:
For fast controlled systems, applications at locations with
temperature variations.
DIP switch 4 OFF and 5 ON:
For normal controlled systems, applications at locations
with normal temperature variations.
DIP switch 4 OFF and 5 OFF:
For difficult controlled systems, 2-position controller with
a switching differential of 0.5 °C (factory setting).
Save the entry by pressing the DIP switch reset button
(also refer to Fig.
).
1.1.5 Periodic pump run: DIP switch 6
Can only be used when circulating pump or valve is controlled!
This function protects the pump or valve against seizing during longer off
periods. Periodic pump run is activated for 3 minutes every 24 hours at 12:00
(display showing symbol ▲).
DIP switch ON:
Periodic pump run on (also refer to Fig.
2
Accessing the expert level
Move the selector slider to the RUN position and press simultaneously
simultaneously
and
settings on that level.
Starting with code 00, the display shows the choice of languages. Navigation on the expert level is made possible with
pressing
.
CE1G2206xx
OFF
1
2
DIP switch reset
Note: The factory setting of all DIP switches is
(factory setting)
(factory setting)
PID self-learning
PID 6
PID 12
2-Point
for 3 seconds, release
and keep
on display (also refer to Fig. G).
3
4
5
6
7
ON
1
2
3
4
5
6
7
DIP switch OFF:
Save the entry by pressing the DIP switch reset button.
1.1.6 Optimum start control: DIP switches 7 and 8
Optimum start control shifts switch on point P.1 such that the adjusted setpoint
will be reached at the required point in time. The setting depends on the type of
controlled system, that is, on heat transmission (piping network, radiators),
building dynamics (building mass, insulation) and heat output (boiler output,
flow temperature)
(also refer to graph in Fig.
DIP switch 7 ON and 8 ON: 1 h/°C
DIP switch 7 ON and 8 OFF: ¼ h/°C
DIP switch 7 OFF and 8 ON: ½ h/°C
DIP switch 7 OFF and 8 OFF: OFF
Save the entry by pressing the DIP switch reset button.
Legend to graph in Fig. .
t
Temperature (°C)
t
Forward shift of switch on point (h)
TRx
Actual value of room temperature
Pon
Start point for optimum start control
).
1.1.7 Heating or cooling mode: DIP switch 9
DIP switch 9 ON:
DIP switch 9 OFF:
Save the entry by pressing the DIP switch reset button
great
(also refer to Fig.
1.1.8 Radio clock: DIP switch 10
Can only be used if receiver DCF77 is integrated (time signal from Frankfurt)!
DIP switch ON:
DIP switch OFF:
Save the entry by pressing the DIP switch reset button
(also refer to Fig.
1.1.9 DIP switch reset (Fig. )
When changing one or several DIP switch positions, press the DIP switch reset
knob to make a DIP switch reset.
Otherwise, the previous settings will be maintained!
(Also refer to Fig.
)
and
for 3 seconds, then release the buttons and, within 3 seconds, press
depressed for another 3 seconds. This enables you to access the expert level for making the
2015-03-18
8
9
10
Periodic pump run on
Periodic pump run off
Optimum start control:1 h/°C
Optimum start control: ¼ h/°C
Optimum start control: ½ h/°C
Optimum start control: Off
(Cooling on)
(Heating on)
Quartz
Radio clock
8
9
OFF
Periodic pump run off (factory setting)
/ 1.1.6).
For slow controlled systems
For fast controlled systems
For medium controlled systems
Off, no impact (factory setting)
.:
Cooling
Heating mode (factory setting)
).
Clock runs on built-in quartz
Time signal DCF77 from Frankfurt
).
)
and
. Confirm the settings by
See
1.1.5
1.1.6
1.1.7
1.1.8
1.1.9
9/56