Mounting notes REV24RF.. and RCR10/868
1
Placement of units
1.1
REV24RF.. and RCR10/868
·
The units must be placed such that transmitted and received signals
will be disturbed as little as possible. For this reason, the following
points must be observed with both the REV24RF.. and RCR10/868:
-
Do not mount the units on metal surfaces
-
Do not mount the units near electrical wires or electronic equipment
such as PCs, TV sets, microwave equipment, etc.
·
Do not mount the units in the vicinity of large metal structures or other
construction elements with fine metal meshes like special glass or
special concrete
·
The distance between controller / transmitter and receiver must not
exceed 20 m or 2 floors
1.2
REV24RF.. (controller / transmitter)
·
The controller / transmitter should be mounted in the main living room
(wall mounting according to Fig. C, free standing according to Fig. E
with stand)
·
The REV24RF.. must be located such that it can acquire the room
temperature as accurately as possible, without getting affected by direct
solar radiation or other heat or refrigeration sources
Wall mounting:
1.3
RCR10/868 (receiver)
·
The receiver and switching unit should preferably be mounted near the
actuating device
·
Make certain that the mounting location is dry and protected from splash
water
·
The unit can be fitted to most commercially available recessed conduit
boxes or directly on the wall
Commissioning RF set
1
Switching on the REV24RF..
·
Remove the black battery transit tab (Fig. F); as soon as the tab is
removed, the unit is ready to operate
2
Selecting the language
·
When starting up, the display shows the type of controller at top left and
"THANK YOU ..." in all available languages on the text line
·
Press one of the buttons to stop the running display. The choice of
languages starts with "ENGLISH" (factory setting). Press
until the language you require appears. Press
confirm the selected language (also refer to Fig. G)
3
Mounting the RCR10/868 temporarily
·
If possible, mount the receiver temporarily (e.g. using double-sided
adhesive tape), thus allowing you to find the location with the best
reception conditions
·
Wire completely the RCR10/868.
For steps to be followed, refer to Figs. H through M (close the front also)
4
RCR10/868 and REV24RF..
·
The units are supplied interconnected
·
For manual connection, refer to operating instructions
5
Mounting and setting up the
REV24RF..
·
Refer to "Mounting instructions REV24RF.. and RCR10/868"
·
Mount or set up the REV24RF.. at your preferred location:
Remove the unit from its baseplate; for procedure, refer to Fig. A
- For wall mounting, refer to Figs. B, C and D
- For setting up, refer to Fig. E
8/56
min.
10 cm
or
or move the slider to
2015-03-18
2
Checking the wiring
For electrical connections, refer to "Connection diagram".
Note:
Do not use stranded wires, only solid wires
or stranded wires with ferrules!
3
Notes
·
The local regulations for electrical installations must be complied with
·
If the reference room is equipped with thermostatic radiator valves, they
must be set to their fully open position
·
External preliminary protection with max. C 16 A circuit breaker is
required in all cases
·
If you wish to check the radio link, press the TEST button at the rear of
the REV24RF..
·
LED_1 is lit red if the RCR10/868 receives very weak or corrupted
control telegrams, or no control telegrams at all for about 65 minutes. In
this case, check the display of the REV24RF.. to see if there is an error
message
·
As long as the RCR10/868 receives control telegrams, the receiver
works normally. If a control telegram is not correctly received, the relay
will maintain the position assumed last.
As soon as the RCR10/868 receives another correct control telegram
from the REV24RF.., the receiver continues to work normally
·
If, for 60 minutes, the RCR10/868 receives no control telegram, or no
correct control telegram, the relay will be deenergized. Hence, the
controlled device is switched off. LED_1 is lit red.
As soon as the RCR10/868 receives another correct control telegram
from the REV24RF.., the receiver continues to work normally
·
In the event of a power failure at the RCR10/868, the relay is switched
OFF
·
Should the REV24RF.. become faulty, the relay of the RCR10/868 can
be controlled manually. As soon as the REV24RF.. resumes correct
operation, its control telegrams will overwrite the relay's manual control.
This process can take up to 130 minutes
·
Press override button
to manually energize and deenergize the
relay. LED_1 indicates manual control by blinking at high frequency.
LED_2 is lit when Lx-L1 is closed (Lx-L2 open). LED_2 is dark when Lx-
L1 is open (Lx-L2 closed)
6
Finding the best place for reception
a)
Switch on the RCR10/868
b)
Set up the REV24RF.. at your preferred location.
Test the radio link by pressing the TEST button at the rear of the controller
(refer to Fig. N1)
c)
The display of the REV24RF.. shows the quality of the radio link. The
longer the bar below the numbers 0...9, the better the quality of the radio
link. If the bar only appears below number 0, there is no secure radio link
(refer to operating instructions)
Insufficient
Sufficient
d)
On the receiver, LED_1 indicates the quality of the radio link (refer to Fig.
N2):
Red
= insufficient or no connection
Orange = good
Green
= very good
e)
If the quality of the radio link is insufficient, reduce the distance between
controller and receiver.
Then, repeat the test
7
Mounting the RCR10/868 in its final
place
a)
Switch power off
b)
Mark the place where the RCR10/868 is located
c)
If necessary, remove wiring
d)
Mount the receiver at the place previously identified (refer to
H through M), complete wiring and close the housing
e)
Switch power on
Good
Very good
Figs.
CE1G2206xx
DE
EN
FR
IT
NL
ES
PT
CS
HU
PL
SV
FI
DA
TR
EL
RO