G e n e r a l i n f o r m a t i o n :
For application in refrigeration systems and heat pumps
according to EN 378.
A professional and appropriate storage and allocation
of the devices is mandatory.
S a f e t y i n s t r u c t i o n s :
• Read operating instructions thoroughly. Failure
to comply can result in device failure, system
damage or personal injury.
• According to EN 13313 this product is intended
for use by personnel having the appropriate
knowledge and skill.
• Ensure that the system is correctly labeled with
applied refrigerant type and a warning for
explosion risk, when used with flammable
refrigerants.
• Before opening any system make sure pressure in
system is brought to and remains at atmospheric
pressure.
• Do
not release any
refrigerant into the
atmosphere!
• Do not exceed the specified maximum ratings for
pressure, temperature, voltage and current.
• Before installation or service disconnect all
voltages from system and device.
• Observe and avoid mechanical damage of housing
in order to maintain protection class.
• Do not use any other fluid without prior approval
of EMERSON. Use of fluids not listed could result
in: Change of hazard category of product and
consequently change of conformity assessment
requirement for product in accordance with
European
pressure
equipment
2014/68/EU.
• Ensure that design, installation and operation are
according
to
European
standards/regulations.
S e t t i n g :
PS4 Pressure switches are factory preset to a specific
value (see label).
F u n c t i o n / T y p e o f s w i t c h : (Fig. 1,2)
Fig.1:
Pressostat -
automatic reset
(NC/NO):
Fig.2: High
pressure cut-out
(manual reset)
PS4 with automatic reset:
PS4 Pressure switches are equipped with snap action
contacts opening or closing on falling or rising
pressure. Depending on model they are equipped with
single pole single through (SPST) or single pole
double through contacts (SPDT).
PS4 with manual reset (HP only):
Reaching the preset switching point contacts open or
close and latches. After the pressure drops by appr.
4-8 bar depending on pressure setting (high pressure
switch only) the switch can be reset by pushing the reset
button.
Emerson Climate Technologies GmbH
Am Borsigturm 31 I 13507 Berlin I Germany
Operating instructions
Pressure Controls Series PS4
I n s t a l l a t i o n :
PS4 Pressure switches should not be exposed to
pulsations. Use a pulsation damper or a capillary tube
connection (min.1m) when pulsations can be expected.
M o u n t i n g l o c a t i o n : a n y
P r e s s u r e c o n n e c t i o n :
Threaded connection:
• Use pulsation damper and high temperature
diaphragm for direct compressor mounted high
pressure applications.
• Do not apply torsional force to switch housing
assembly during assembly.
(1) = Copper
gasket
Brazing:
• Perform the
brazing as per
EN 14324.
• Before and after
brazing clean
tubing and
brazing joints.
• Do not exceed
the max. body
temperature of
70°C!
P r e s s u r e T e s t :
directive
After completion of installation, a pressure test must be
carried out as follows:
- according to EN 378 for systems which must
and
national
comply with European pressure equipment
directive 2014/68/EU.
- to maximum working pressure of system for other
applications.
Warning:
• Failure to do so could result in loss of refrigerant
and personal injury.
• The pressure test must be conducted by skilled
personnel with due respect regarding the danger
related to pressure.
T i g h t n e s s T e s t :
Conduct a tightness test according to EN 378-2 with
appropriate equipment and method to identify leakages
of external joints. The allowable leakage rate must be
according system manufacturer's specification.
E l e c t r i c a l c o n n e c t i o n :
• Comply with local electrical regulations when
wiring PS4. To maintain protection class, proper
installation is mandatory.
• Ensure that the cables are mounted without
tension; always leave the cable a bit loose.
• Ensure that cables are not mounted near sharp
edges.
O p e r a t i o n :
Perform a functional test of electrical circuit
before charging the system with refrigerant.
S e r v i c e / M a i n t e n a n c e :
• Disconnect electrical power before service.
• Defective PS4-... must be replaced; they cannot be
repaired.
• In case of repair work or replacing the control always
use new gasket Fig 3 (1).
www.climate.emerson.com/en-gb
Fig.3
T e c h n i c a l D a t a :
Protection class
(IEC 529/ DIN 40050)
Temperatures
Ambient (housing)/
Storage/ transport
Medium
Vibration resistance
Pressure range
Setting
Series PS4
(bar)
0 < 6.9
7 - 27.6
all except:
PS4-B/ R
27.7 - 38
38.1 - 50
13.8-27.6
27.7 - 38
PS4-B/R
38.1 - 50
Electrical rating
230 V AC
PS4-
Ind.
A, W
B, R
For electronic applications with low electrical loads
(current <100 mA) standard contacts are not suitable. The
use of gold-plated contacts is recommended.
Type
Fig.4
Gold contact (5...24 V)
Fluid Group
Hazard Category
(PED 2014/68/EU)
Refrigerants (ASHARE)
Marking
Low Voltage Directive & ENEC05
0035 Pressure Equipment Directive
No. E258370 (A2L pending)
PS4 - ① ②
T y p e c o d e :
① Function
e.g.
PS4 – A 1
A Pressure controls, automatic, high pressure or low
pressure
W Pressure limiters, automatic, type approval acc.
EN 12263, (Definition term by EN12263 & EN378:
PSL/PSH)
R Pressure controls, external manual reset (by hand)
B Pressure limiters, external manual reset (by hand);
type approval, acc. EN 12263, (Definition term by
② Electrical connection
EN12263 & EN378: PZH)
1 Normally closed silver contact with molded cable
2 Normally open silver contact with molded cable
3 Normally closed silver contact with quick
connector; QC (for push-on spades)
4 Normally open silver contact with quick connector,
QC (for push-on spades)
5 Normally closed gold-plated contact with molded
cable
L Normally closed silver contact with molded cable
suitable for manual rest
PS4_OI_EN_DE_FR_ES_IT_RU_0521_R05_865025.docx
IP67
IP20
(Terminal connection)
-40...+65 °C
-40...+135 °C
4 g (10...250 Hz)
Operating
Test
pressure PS
pressure PT
(bar)
(bar)
22.7
25
37
41
50
55
63
69
37
41
50
55
63
69
<28 V DC
LRA
Ind.
(A)
(A)
(A)
6
2
36
6
2
15
A
W
B
R
25-250 mA
-
-
I & II
IV / Module B + D
A1 + A2L
Mineral-. Synthetic-.
POE-Lubricant
Date: 18.05.2021

Publicité

loading

Sommaire des Matières pour Emerson PS4 Serie

  • Page 1 (current <100 mA) standard contacts are not suitable. The • Do not use any other fluid without prior approval the max. body use of gold-plated contacts is recommended. of EMERSON. Use of fluids not listed could result temperature of Type in: Change of hazard category of product and 70°C!
  • Page 2 Schutzklasse erhalten bleibt. überschreiten! hierfür werden Goldkontakte empfohlen. • Es dürfen nur von EMERSON freigegebene D r u c k t e s t : Medien eingesetzt werden. Die Verwendung nicht Nach der Installation ist ein Drucktest durchzuführen:...
  • Page 3 • Ne pas utiliser un autre fluide que ceux indiqués contacts dorés 5…24 V) 25-250 mA Après le montage, un test de pression doit être fait en sans l’approbation obligatoire d’EMERSON. I & II Groupe de fluide respectant: L'utilisation d'un fluide non approuvé peut Catégorie de risque...
  • Page 4 • No use ningún fluido que no haya sido 25-250 mA Fig.4 (5…24 V) previamente aprobado por EMERSON. El uso de No sobrepasar la máxima temperatura de 70ºC. • sustancias no aprobadas puede dar lugar a un I & II Grupo de fluido P r u e b a d e p r e s i ó...
  • Page 5 • PS4-… difettosi devono essere sostituiti, non è presenti pulsazioni. Si richiede un attenuatore di possibile la riparazione. pulsazioni o un capillare di almeno 1 mt. se sono presenti pulsazioni. Emerson Climate Technologies GmbH www.climate.emerson.com/en-gb Date: 18.05.2021 Am Borsigturm 31 I 13507 Berlin I Germany PS4_OI_EN_DE_FR_ES_IT_RU_0521_R05_865025.docx...
  • Page 6 от настройки (только для реле ВД), реле можно всегда используйте новые прокладки Рис.3 (1). кабелем, для ручного сброса аварии. вернуть в исходное положение нажатием кнопки возврата. Emerson Climate Technologies GmbH www.climate.emerson.com/en-gb Date: 18.05.2021 Am Borsigturm 31 I 13507 Berlin I Germany PS4_OI_EN_DE_FR_ES_IT_RU_0521_R05_865025.docx...