Power Wiring Interconnections
All wiring must be the proper size, properly supported
and protected by conduit. All wiring should be done
per applicable federal, state and local codes, standards
and regulations. Obey wire type and torque specifications
printed on the terminal blocks and neutral/ground connector.
WAR NING Low voltage wire cannot be installed in
same conduit as power voltage wiring.
•
Failure to follow above warning could cause personal
injury, damage and/or malfunction of equipment.
NOTICE Improper installation can cause damage to the
circuit boards and shorten their life. Installing circuit
boards in live circuits will damage the board and is not
covered by warranty. ALWAYS disconnect ALL sources of
power prior to servicing.
•
Remove all power prior to installing this equipment.
Failure to do so could cause internal damage to the board
when making electrical connections.
•
Turn generator to
OFF position.
•
Turn off utility power to the standby generator and
transfer switch.
Existing fuse
Optional
holder
fuse holder
WARNING Battery posts, terminals and related
accessories contain lead and lead compounds, chemicals
known to the State of California to cause cancer and
reproductive harm. Wash hands after handling.
Complete the following connections between the
transfer switch, the power management system and the
main distribution panel. Also see Wiring Decal, later in
this manual.
1. Set generator's system switch to OFF position.
2. Set generator's circuit breaker to OFF (open) position.
3. In main distribution panel, identify loads and their
priorities (using list developed with owner) that will be
'managed' by the system. An Electrical Load Worksheet
is provided.
4. In main distribution panel, turn selected load circuit
breakers to OFF position.
5. Connect "GND" lug to an approved ground.
NOTE: Assure grounding electrode conductor is connected
and bonded per applicable federal, state and local codes,
standards and regulations.
To current
TEST
transformers
button
To air conditioning control
wiring (A1 and A2).
A3 and A4 are lockouts
To 50A MAX
general
purpose
loads
To
GROUND
7