Preparing A Duct System For Testing - Lindab LT 600 Mode D'emploi

Masquer les pouces Voir aussi pour LT 600:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

5. Preparing a duct system for testing

Figure 3: Connection to the duct system
The duct system should be tested in accordance with
DIN EN 12237, DIN EN 1507, DIN EN 1507 and DIN EN
12599 A speci c pressure may be stipulated as stated
in the standards
Any positive or negative target pressure can be
selected within the measuring range If the duct system
is particularly large or complex, leakage testing can
be restricted to sections of the system (See DIN EN
12599)
DIN EN 12599 compliant leakage testing should be car-
ried out while the duct system is being installed, when
the ducts are still accessible (for example they have not
been insulated yet) The duct surface area being tested
should always be greater than 10 m² The duct surface
area should be measured and calculated as de ned in
DIN EN 14239, and should be established in advance
You are recommended to estimate the anticipated leak-
age ow rate in advance (see the appendix)
Before you start testing, seal off the duct section being
tested from the rest of the system All openings, out-
lets, etc must be carefully sealed
It is extremely important to seal properly around
the openings and the test connections.
The connecting points in the duct system being tested
must be de ned in advance, for the 50 mm air hose as
well as the thin pressure measuring tube The connect-
ing points should be about 2 m apart from each other
to prevent one affecting the other
Use suitable joints to prepare the connections for the
50mm air hose and the pressure measuring tube
Do not subject the hose connections to torsional
stresses.
Use the connection on the front (10) for positive
pressure, and the connection on the top (5) for
negative pressure.
Always use adapters on the front, even for negative
pressure testing.
6
Next, attach the thin pressure measuring tube to the
"+" connection (2) on the front, to the left above the 50
mm connection
The pressure measuring tube is always attached
to the "+" connection (2). The device automatically
detects positive pressure and negative pressure.
The "-" connection (3) must be left clear.
A bayonet closure is used for the "+" connection of the
pressure measuring tube: turn clockwise to lock and
counterclockwise to open
In principle, you should always start the leakage
test initially without an adapter After you nd out
the leakage ow rate, you can use the relevant adapter
to improve the measuring accuracy See page 4 The
adapters have different names, indicating the maximum
measurable ow rate in l/s
DIN EN 15727 compliant measurements usually use
lower ow rates and are carried out in the same way It
is also possible to depart from the recommended spac-
ing of 2 m between the hose and the tube In order to
take measurements on the pressure side for very small
components, the thin 4m tube can be plugged directly
into the adapter instead of the 50 mm hose, and a
nipple connection is used with the component