About the chart:
The bar chart shows the permitted leakage ow rate for the airtightness classes, with the speci ed m² and the actual
test pressure The test value appears as a red line
Compliant airtightness classes are shown with green bars Non-compliant classes are shown with red bars
10
Shows the con gured parameter and the maximum permitted leakage ow
rate
• Press the to start the test
• A self test is carried out before the test starts
• The test starts once the selected pressure is reached, and continues for
ve minutes
• You can interrupt the test at any time by pressing Stop
While the test is running, the achieved pressure and the current ow rate
are displayed
• After the test duration of 300 s, the device stops automatically (Stand-
ardised test duration) If you press Stop to end the test early, the results
are displayed
• The device indicates whether the test has passed or failed with the
specifi d parameters
• Press the Print key to print the report or press the New key to start a
new test
Viewing the report before printing
• You can use the or key to scroll through the report
• Switch on the TD 600 printer and place it close to the IR window
• Press OK to start printing
• Note: The report is not permanently stored unless you select "Save" on
the menu
Chart:
• Press the MENU key and press the or key to select Chart from the
menu
• Con rm by pressing the key
• You can print the chart by pressing the Print key on the TD 600
• To return to the menu press the Menu or New key once
• To start a new test, press the Menu key twice