4
TECHNICAL DATA
Technical data CA 462
4.1
Temperature input threshold (±10%)
Max PTC current
PTC source voltage
Leakage sensor voltage
Max leakage sensor current
Leakage detection threshold (±10%)
Leakage alarm delay
Ambient operating temperature
Ambient storage temperature
Degree of protection
Housing material
Mounting
Installation category
Pollution degree
Flame rate
Humidity
Dimensions
Power supply
Fuse
Terminal wire size
Terminal tightening torque
Power consumption
Max load alarm relays
Altitude
Max load output pump blocking relay
Compliance
Attention
If the unit is used in a manner not described in this document the protection provided by the equipment may be
impaired.
> 3.3 kohm (PTC / Klixon)
< 0.6 mA
12 VDC
12 VDC
< 15 µA
< 100 kohm
10 seconds
–20 to +50 °C (–4 to +122 °F)
–30 to +80 °C (–22 to +176 °F)
IP 20, NEMA: Type1
PPO and PC
DIN Rail 35 mm
CAT II
2
V0 (E45329)
0–95% RH non-condensing
H x W x D: 108 x 70 x 58 mm
(4.25 x 2.76 x 2.28 inch)
16907006
110-230 VAC, 50 Hz/60 Hz
18-36 VDC SELV or Class 2
16907007
Max 10 A
Use copper (Cu) wire only. 0.2 - 2.5 mm
flexible core, stripped length 8 mm.
0.56 - 0.79 Nm (5 -7 lbs-in)
< 5 W
250 VAC 3 Ampere resistive load
Max 2000 MASL or 6562 ft. AMSL
250 VAC 6 Ampere resistive load
9
2
EN