TILSLUTNINGSDIAGRAM
Electrical connection
2.1
If several sensors are to be used from the pump, then they must be connected together.
sensors must be in parallel
Leakage:
It is very important to have in mind that this practice avoids alarms to be distinguished. Sulzer
highly recommends to use one module per signal to allow not only distinguishing but also acting
in a different way according to the alarm category/severity.
Temperature (Klixon or PTC): sensors must be in series
PTC eller
Klixon
Tilslut terminal 12 til jord
eller pumpehus
Elektrisk tilslutningsdiagram
Figur 1
When several CA 462 units are used, the reset buttons cannot be wired together. The solution is to use one
reset button to each unit or an external relay which control all the reset buttons as figure 2.
Reset all CA 462
External relay
Connection of reset function for multiple CA 462 units
Figur 2
Hvis pumpen betjenes fra et motordrev eller en frekvensomformer, kræves der særlige forholds-
regler.
Det høje elektriske støjniveau kan forvrænge elektriske aflæsninger og i forlængelse heraf bringe funk-
tionaliteten i fare. For at undgå elektrisk støj følg bedste praksis og producentens EMC-overensstemmelsesan-
befalinger, når der installeres frekvensomformere. Brug afskærmede kabler og 50 cm adskillelse mellem
strøm- og signalkabler. Kontroller, at kablerne også er adskilt fra hinanden i skabene.
Pumpkontaktor
frakobles
Strømfor-
syning
Leakage
sensors
CA 462
Reset CA 462 - ...n
Reset CA 462 - 2
Reset CA 462 - 1
71
Udgang
Temperaturalarmrelø
Udganglækage
alarmrelæ
Tilkoblet, hvis der anmodes
om manuel nulstilling
Nulstillingskontakt