SCHEMA ELETTRICO
Electrical connection
2.1
If several sensors are to be used from the pump, then they must be connected together.
sensors must be in parallel
Leakage:
It is very important to have in mind that this practice avoids alarms to be distinguished. Sulzer
highly recommends to use one module per signal to allow not only distinguishing but also acting
in a different way according to the alarm category/severity.
Temperature (Klixon or PTC): sensors must be in series
PTC o
Klixon
Collegare il terminale 12
a terra o alla carcassa
della pompa
Figura 1 Schema elettrico
When several CA 462 units are used, the reset buttons cannot be wired together. The solution is to use one
reset button to each unit or an external relay which control all the reset buttons as figure 2.
Reset all CA 462
External relay
Figura 2 Connection of reset function for multiple CA 462 units
Se la pompa è avviata da un azionamento a motore o da un convertitore di frequenza, sono necessa-
rie precauzioni speciali.
L'elevato livello di rumore elettrico può distorcere le letture elettriche e, per estensione, compro-
mettere la funzionalità. Per evitare rumori elettrici condotti, seguire le migliori pratiche e le rac-
comandazioni di conformità EMC del produttore quando si installano i convertitori di frequenza.
Utilizzare cavi schermati e 50 cm di distanza tra i cavi di potenza e di segnale. Assicurarsi che
anche i cavi siano separati tra loro all'interno degli armadietti.
Manovra contattore
pompa
Alimentazione
Leakage
sensors
CA 462
Reset CA 462 - ...n
Reset CA 462 - 2
Reset CA 462 - 1
79
Uscita
Relè di allarme
temperatura
Uscita Infiltrazione
Relè di allarme
Collegato con ponte se
è richiesto reset manuale
Interruttore di reset