Note on adjustment dimensions for tanks as per EN 12285-1 and
EN 12285-2:
Respect all directives, standards and safety regulations applicable at the
installation site with regard to the permissible filling degree.
The adjustment dimensions X in the tables were calculated for class C
tanks. In the case of class A and class B tanks with a lesser material thick-
ness of the manhole cover, the difference in material thickness may be
subtracted from the table values for the adjustment dimension.
If a tank diameter is not contained in the tables, you can use the adjust-
ment dimension for the next greater tank diameter if the tank volume is
identical.
If a tank volume is not contained in the tables, you can use the adjustment
dimension for the next lower tank volume if the tank diameter is identical.
Tank Ø
Volume
[mm]
tank/
compart-
ment [m
900
1
1000
1
1250
1
1.5
2
3
Table 7: Cylindrical vertical tanks as per EN 12285-1 and EN 12285-2 with
permissible filling degree 95 % (V/V)
Mounting
Response
Adjust-
level h
ment
[mm]
dimen-
sion X
3
]
[mm]
660
355
730
385
910
455
970
395
1005
360
1040
325
GWG 23-Ro / GWG 23-Wa / GWG 23-T
Check dimension Y [mm] at
probe length
400
500
700
45
145
345
15
115
315
-
45
245
5
105
305
40
140
340
75
175
375
EN
1000
645
615
545
605
640
675
24