Fig. 11
Connection up to 240 mm²
L 1, L 2, L 3
Nut M12 40 Nm
Lock washer and
washer M12
Cable lug
Connection plate
Copper rail
Screw hook M12
Fig. 14
Connection up to 70 mm²
L 1, L 2, L 3
Nut M10 20 Nm
Lock washer and
washer M10
Cable lug
Connection plate
Copper rail
Screw hook M10
Fig. 17
Bus bar system 630A
Enclosure seal
Enclosure wall
18
18
18
18
18
Cooper Crouse-Hinds GmbH
Explosion-protected terminal and bus bar boxes, type
GHG 75.
Fig. 12
Connection up to 240 mm²
(single rail connection) N, PE
Screw hook M12
Fig. 15
Connection up to 70 mm²
(single rail connection) N, PE
Screw hook M10
Warning: Each rail shall be safeguarded
against displacement using the shift
protection.
The minimum clearances between the
enclosure wall and the bus bars, as well as
between the connections shall be
maintained.
Extension
system 630 A
Fig. 13
Shift protection
Nut M12 40 Nm
Lock washer and
washer M12
Cable lug
Connection plate
Copper rail
Spacer
Fig. 16
Extension system
Nut M10 20 Nm
Lock washer and
washer M10
Cable lug
Connection plate
Copper rail
Spacer
Shift protection
Nut M10 20 Nm
Lock washer and
washer M10
Clamp plate
Copper rail
Clamp plate
Washer M10
Hex-head screw M10
Nut M12 40 Nm
Lock washer and
washer M12
Extension plate
Copper rail
Screw hook M12