12. Filling the tank

Fill tank with coolant (water-glycol mixture in the appropriate concentration) until the maximum level is
reached (water quality and treatment should be established according to the application specifications)
Chiller circuit is designed with non-ferrous materials: stainless steel, brass, copper, bronze, Polyethylene,
rubber etc.
To speed up the filling procedure it is recommended to fill-in the user circuit as well.
For standard application with a minimum ambient temperature +13 °C the suggested fluid is:
Pfannenberg Protect PP20E
CAUTION
Do not use any automotive antifreeze
Do not use distilled water
Do not use other fluids or additives which the chemical composition is not well known
In case of any doubt contact Service Pfannenberg.

13. Electrical connection

DANGER
Life-threatening danger due to electric shock
Live units and exposed connection cables can generate an electric shock and cause severe accidents.
➢ Work on electrical connections must be carried out exclusively by trained, qualified electricians.
➢ Switch OFF the electrical power before wiring the power cord.
➢ To avoid accidents, turn the main switch of the customer's e-box to the OFF position and lock it.
Appendix I - Fig. 5
➢ Test to ensure the absence of voltage on the unit and on all power supply cables.
➢ Lightning protection of the unit (outdoor installation) must be carried out by qualified engineers.
Electrical power supply cables and protections should be sized according to the technical data of the unit
and according to the local and power distributor Standards.
Electrical power supply cables should be carried into the electrical box and ensure by the connecting
glands in the bottom side of electrical box.
Connect the ground conductor yellow-green to the PE terminal block in the electrical box.
Connect the electrical power supply cables direct to the main switch QS0 following the right phase
sequence.
Do not switch on the electrical power the chiller if it has been moved from a cold to warm environment.
Humidity inside the electrical devices could cause condense water and consequent damage.
Check that the voltage supply is according to the electrical data in the type label.
Check that the transformer of auxiliary circuit is correctly connected in conformity to the supply voltage and
frequency.
Appendix I - Fig. 6