COMBUSTION AIR INTAKE DIRECTLY FROM THE INTALLATION ROOM
It's advisable to read, follow and respect what indicated in the Section Installation.
•
The equipment should have the necessary air for combustion, supplied by external air
•
intake.
The air intake should have the following characteristics :
•
a)
Total free section min 200 cm²;
b)
Connected directly with the installation room;
c)
Protected with grate or lath (attention to not reduce the min. section required on
point a) and placed so as to avoid obstructions.
The air inflow can be also supplied from an adjacent room, but the air intake should be
•
always free and connected with the outside. No chimney or suction hood should be
present in the installation room or in the adjacent ones.
Inside the adjacent room the air intake should have the characteristics required in letter a
•
and c .
The adjacent room should not be use as garage, warehouse of combustible material etc..
•
FEED AIR COMBUSTION DIRECT FROM OUTSIDE
It's advisable to read, follow and respect what indicated in the Section Installation.
•
To take air direct from outside it's necessary :
•
Use metal tubes of diameter Ø50 mm or more; resistant to temperature of al least
−
200°C in this area of connection to the appliance.(See the connection schedule).
To guarantee a sufficient air influx, the connection's tube has not to be longer that
−
2÷3 mt. and it has not to have a lot of curves.
If the air intake is direct to outside, its output has a curve of 90° down with a
−
protection grill to avoid the introduction of small animals.
In case of closure device, it must open automatically at equipment's starting.
−
To not observe these instructions, it means that Your stove will have a bad
−
combustion and the lost of Your guarantee.
Protected with grate or lath ( attention to not reduce the min. section required on
−
point a ) and placed so that to avoid obstruction .
NOTE: the air inlet for ventilation situated in the installation environment should be placed
below.
NOTE : Extractor fans when operating in the same room or space as the appliance may cause
problems.
NOTE :The installation room should not be put in depression by other appliances such as
suction hoods, chimneys, evacuation flues, present in the room itself or in the adjacent rooms,
which are in communication.
IT IT IT IT- - - - GB
GB- - - - FR
FR- - - - ES
GB
GB
FR
FR
48/140
ES mod. 540 VT – 540N VT
ES
ES