4 - MODBUS PROTOCOL (INPUT REGISTERS)
MODBUS ADRESS
1
SOFTWARE VERSION H (CONTROL BOARD) (4 first chars)
2
SOFTWARE VERSION L (CONTROL BOARD) (4 last chars)
3
SOFTWARE VERSION H (POWER BOARD) (4 first chars)
4
SOFTWARE VERSION L (POWER BOARD) (4 last chars)
5
MAXIMUM MOTOR CURRENT (POWER BOARD)
6
STOP/AUTO
7
CURRENT SETPOINT
8
ACTUAL PRESSURE
9
ACTUAL TEMPERATURE
10
4-20mA INPUT 1
11
4-20mA INPUT 2
12
0-10V INPUT
13
PTC/NTC INPUT
14
DIGITAL INPUT 1
15
DIGITAL INPUT 2
16
DIGITAL INPUT 3
17
DIGITAL INPUT 4
18
RELAY 1 OUTPUT
19
RELAY 2 OUTPUT
20
EXPANSION BOARD CONNECTED
21
ALARM CODE (POWER BOARD)
22
MOTOR ACTUAL FREQUENCY
23
MOTOR ACTUAL CURRENT
24
POWER MODULE TEMPERATURE
25
CONTROL AMBIENT TEMPERATURE
26
ACTUAL MOTOR POWER
27
ACTUAL NETWORK POWER
28
POWER ON HOURS (MSB)
29
POWER ON HOURS (LSB)
30
OPERATING HOURS (MSB)
31
OPERATING HOURS (LSB)
32
START-UP NUMBER COUNTER (MSB)
33
START-UP NUMBER COUNTER (LSB)
34
ALARM F01 COUNTER
35
ALARM F02 COUNTER
36
ALARM F03 COUNTER
37
ALARM F04 COUNTER
VALUE / PARAMETER
246
UNITS
HEX
HEX
HEX
HEX
0.1A
0.1Bar / PSI
0.1Bar / PSI
0.1ºC / 0.1ºF / ***
0.1mA
0.1mA
0.1V
0.1 kohm
0/1
0/1
0/1
0/1
0/1
0/1
0/1
0.1Hz
0.1Hz
ºC
ºC
W
W
s
s
s
s