4. survey and technical data

Temperature
range
controller 0 up to +50°C
0 up to +200°C
+50 up to +300°C
limiter
+20 up to + 150°C
+130 up to +200°C
+20 up to +400°C
Technical data:
Voltage:
Frequency:
Breaking capacity controller:
Breaking capacity limiter:
Protective class:
Environmental protection:
Working temperature:
Hysteresis:
Accuracy
Enclosure:
Glands:
Dimensions:
Weight:
Length of capillary tube:
Material of capillary tube:

5. accessories

The following support brackets are available for T-M-20-S: SB-120
8
sensor
temperature
max.
+60°C
+230°C
+345°C
+170°C
+230°C
+500°C
230 V AC
50 / 60 Hz
16 A / 230 VAC
10 A / 230 VAC
I
IP 65
-20 up to +80°C
2.5% of temperature range
±0,5% of setpoint in upper third
of temperature range (at 22°C
ambient)
Polyester
2 x M20 + 1 x M25 incl. reducer
M25/M20
220 x 120 x 90 mm
1.8 kg
appr. 2 m
V4A Stainless Steel
order reference
T-M-20-S/0+50C
T-M-20-S/0+200C
T-M-20-S/+50+300C
T-M-20-S/0+50C
T-M-20-S/0+200C
T-M-20-S/+50+300C