THREE PHASE POWER UNBALANCE

A full three phase supply consisting of three individual
transformers or one three phase transformer is recom-
mended. "Open" delta or wye connections using only
two transformers can be used, but are more likely to
cause poor performance, overload tripping or early
motor failure due to current unbalance.
Check the current in each of the three motor leads
and calculate the current unbalance as explained
below.
If the current unbalance is 2% or less, leave the leads
as connected.
If the current unbalance is more than 2%, current
readings should be checked on each leg using each
of the three possible hook-ups. Roll the motor leads
across the starter in the same direction to prevent
motor reversal.
Starter Terminals L1
Motor Leads
R
T3
Example:
T3-R = 51 amps
T1-B = 46 amps
T2-W = 53 amps
Total = 150 amps
4 ÷ 50 = .08 or 8%

INSULATION RESISTANCE READINGS

Normal Ohm and Megohm Values between all leads and ground
Condition of Motor and Leads
A new motor (without drop cable).
A used motor which can be reinstalled in well.
Motor in well. Readings are for drop cable plus motor.
New motor.
Motor in good condition.
Insulation damage, locate and repair.
Insulation resistance varies very little with rating. Motors of all HP, voltage and phase ratings have similar values of
insulation resistance.
Insulation resistance values above are based on readings taken with a megohmmeter with a 500V DC output.
Readings may vary using a lower voltage ohmmeter, consult factory if readings are in question.
Hookup 1
L2
L3
B
W
T1
T2
÷ 3 = 50 amps
– 46 = 4 amps
To calculate percent of current unbalance:
A. Add the three line amp values together.
B. Divide the sum by three, yielding average current.
C. Pick the amp value which is furthest from the aver-
age current (either high or low).
D. Determine the difference between this amp value
(furthest from average) and the average.
E. Divide the difference by the average. Multiply the
result by 100 to determine percent of unbalance.
Current unbalance should not exceed 5% at service
factor load or 10% at rated input load. If the unbal-
ance cannot be corrected by rolling leads, the source
of the unbalance must be located and corrected. If, on
the three possible hookups, the leg farthest from the
average stays on the same power lead, most of the
unbalance is coming from the power source.
Contact your local power company to resolve the
imbalance.
Hookup 2
L1
L2
L3
W
R
B
T2
T3
T1
T2-W = 50 amps
T3-R = 48 amps
T1-B = 52 amps
Total = 150 amps
÷ 3 = 50 amps
– 48 = 2 amps
2 ÷ 50 = .04 or 4%
Ohm Value
20,000,000 (or more)
10,000,000 (or more)
2,000,000 (or more)
500,000 - 2,000,000
Less than 500,000
Hookup 3
L1
L2
L3
B
W
R
T1
T2
T3
T1-B = 50 amps
T2-W = 49 amps
T3-R = 51 amps
Total = 150 amps
÷ 3 = 50 amps
– 49 = 1 amps
1 ÷ 50 = .02 or 2%
Megohm Value
20 (or more)
10 (or more)
2 (or more)
.5 - 2
Less than .5