Safety Instructions; Conformity With Standards; Field Of Application - Cooper Crouse-Hinds CEAG GHG 516 Mode D'emploi

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Dimensions in mm
X = fixing dimensions
Coupler 3-pole
Coupler 4-pole
Coupler 5-pole
Flange socket 3-pole
Flange socket 4-pole
Flange socket 5-pole
Drilling template for flange sockets
8 8 8 8 8
COOPER Crouse-Hinds GmbH
Explosion protected plug and socket system
16A, GHG 516
2

Safety instructions

The GHG 516 plugs and sockets
are not suitable for Zone 0
and Zone 1 hazardous areas.
The temperature class and explosion
group marked on the apparatus shall be
observed.
Modifications to the plugs and sockets or
changes of their design are not permitted.
They shall be used for their intended
purpose and in perfect and clean condition.
For replacement and repair only genuine
COOPER CROUSE-HINDS / CEAG spare
parts shall be used.
Repairs that affect the explosion protection,
may only be carried out by Cooper
Crouse.Hinds or a qualified electrician in
compliance with the respective national
regulations.
Prior to taking the plugs and sockets into
operation, they will have to be checked in
accordance with the instruction as per section 6.
The sockets may only be used with the
associated COOPER CROUSE-HINDS /
CEAG plugs in undamaged condition.
The interlocking switch of the socket is
mechanically secured by means of spring-
loaded locking pins and cannot be
connected without plug.
Before the initial operation, any foreign
matter will have to be removed from the
the plugs and sockets.
Observe the national safety rules and
regulations for prevention of accidents as
well as the safety instructions included in
these operating instructions and set in
italics the same as this text!
3

Conformity with standards

The apparat is conform to the standards
specified in the EC-Declaration of conformity.
It has been designed, manufactured and
tested according to the state of the art and to
DIN EN ISO 9001.
3-pole
94/9 EC: Equipment and protective systems
intended for use in potentially explosive at-
mospheres.
The apparats fulfil further requirements, such
as the EC directive on electromagnetic
compatibility (2004/108/EEC)
4 / 5-pole
4

Field of application

The plugs and sockets GHG 516 are suitable for
use in Zone 2 hazardous areas acc. to
IEC 60079-10!
The enclosure materials employed, including the
exterior metal parts, are made of high-quality
materials which ensure a corrosion protection and
resistance to chemical substances corresponding
to the requirements in a "normal industrial
atmosphere":
- impact resistant polyamide
- glass-fibre reinforced polyester
- special steel AISI 316 L
In case of use in an extremely aggresive
atmosphere, please refer to manufacturer.
5
Use/Properties
The GHG 516 plugs and sockets are used for the
power supply of local controls with varying loca-
tions, as well as of electrical installations, mobile
machinery and driving gear in hazardous areas.
The plugs and sockets can also be used in a
„normal industrial area".
The low-voltage plugs and sockets GHG 516
are fitted with a load switch and can be used
up to max. 16 A (see technical data).
The plugs and sockets can generally be used
for the voltage range laid down in IEC 309
(e.g. U
400V that corresponds to the voltage
N
range 380-415V).
The apparatus connected to the plug shall
be suitable for the applied mains voltage.
In order to switch on the socket, the plug is
inserted, pushed fully home and then turned
through approx. 45° to the right. Thereby the plug
is locked in the socket (see page 9, fig. 1).
For switching off and pulling the plug, proceed in
inverse order.
After separating the plug from the socket, the
latter shall be closed with the hinged cover and
secured with the bayonet ring.
The plug can be pushed into the socket and
pulled out of it only whilst the socket is switched
off.
In order to activate the socket, the plug is pushed
fully home. Then the switching ring on the plug
can be turned through 45° to the right in order to
unlock the interlocking switch (see page 9 fig.1)!.
In order to ensure the socket's type of protection
acc. to the type label also with the plug being
inserted, the bayonet ring of the plug (page 9, fig.
2, item 2) is turned to its stop onto the socket.
The data as per point 3 and 4 will have to
be taken into account with the use.
Applications other than described are not
permitted without COOPER CROUSE-
HINDS / CEAG's prior written consent.
For the operation, the instructions stated in
section 7 of the operating instructions will
have to be observed.
From time to time, the locking function
protecting against inappropriate use e. g. of
industrial plugs in zone 2 has to be
checked.

Publicité

Table des Matières
loading

Table des Matières