Victron energy BMV 600 Manuel page 18

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

calculation is also linked to this value. It is recommended to keep
this value at around 50.0%.
ClS:
Clear SOC relay. When the state-of-charge percentage has risen
above this value, the alarm relay will be de-activated. This value
needs to be greater than or equal to DF.
RME:
Relay minimum enable time. Specifies the minimum amount of
time that the alarm relay should be enabled once an alarm condition
has occurred.
Relay disable delay. Specifies how long you have to wait before
RDD:
disabling the relay; after the alarm condition has cleared.
Al:
Alarm low voltage (buzzer). When the battery voltage falls below
this value for more than 10 seconds a bell icon appears on the
display, the backlight flashes, and the buzzer will sound. The buzzer
and backlight-flashing can be turned off by pressing any key; the
bell-icon will remain on the display.
Alc:
Clear low voltage alarm. When the battery voltage rises above this
value, the alarm is turned off. This value needs to be greater than or
equal to Al.
Ah:
Alarm high voltage (buzzer). When the battery voltage rises above
this value for more than 10 seconds a bell icon appears on the
display, the backlight flashes, and the buzzer will sound. The buzzer
and backlight-flashing can be turned off by pressing any key; the
bell-icon will remain on the display.
Ahc:
Clear high voltage alarm. When the battery voltage falls below this
value, the alarm is turned off. This value needs to be less than or
equal to Ah.
AS:
Alarm low SOC (buzzer). When the state-of-charge falls below this
value for more than 10 seconds a bell icon appears on the display,
the backlight flashes, and the buzzer will sound. The buzzer and
backlight-flashing can be turned off by pressing any key; the bell-
icon will remain on the display.
ASc:
Clear low SOC alarm. When the state-of-charge rises above this
value, the alarm is turned off. This value needs to be greater than or
equal to AS.
Rl:
Relay low voltage. When the battery voltage falls below this value
for more than 10 seconds the alarm relay will be activated.
Rlc:
Clear relay low voltage. When the battery voltage rises above this
value, the alarm relay will be de-activated. This value needs to be
greater than or equal to Rl.
Rh:
Relay high voltage. When the battery voltage rises above this
value for more than 10 seconds the alarm relay will be activated.
Rhc:
Clear relay high voltage. When the battery voltage falls below this
value, the alarm relay will be de-activated. This value needs to be
14

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Bmv 602

Table des Matières