1�2
Switch GHG 252 ��
Dependence on connection cross section / current load / ambient temperature
Enclosure size 1
Enclosure size 2
Enclosure size 3
16
Explosion-protected switch
GHG 252
Ex25S2
16 A
2,5 mm²
T6
T6
4,0 mm²
T6
T6
Ex25S2
16 A
2,5 mm²
T6
T6
4,0 mm²
T6
T6
6,0 mm²
T6
T6
Ex25S2
16 A
2,5 mm²
T6
T5
4,0 mm²
T6
T6
6,0 mm²
T6
T6
10,0 mm²
T6
T6
16,0 mm²
T6
T6
20 A
25 A
T6
-
T5
-
T6
T6
T6
T5
20 A
25 A
T6
-
T5
-
T6
T6
T6
T5
T6
T6
T6
T6
20 A
25 A
T5
-
T4
-
T6
T5
T5
T4
T6
T6
T6
T6
T6
T6
T6
T6
T6
T6
T6
T6
32 A
max. 4 pole
incl. 1 aux switch
AUX-S
-
TU=+40 °C
-
TU=+55 °C
T5
TU=+40 °C
T4
TU=+55 °C
32 A
max. 4 pole
incl. 2 aux switches
AUX-S
-
TU=+40 °C
-
TU=+55 °C
T5
TU=+40 °C
T4
TU=+55 °C
T6
TU=+40 °C
T5
TU=+55 °C
32 A
max. 8 pole
incl. 2 Aux switches
AUX-S
-
TU=+40 °C
-
TU=+55 °C
T4
TU=+40 °C
T4
TU=+55 °C
T6
TU=+40 °C
T5
TU=+55 °C
T6
TU=+40 °C
T6
TU=+55 °C
T6
TU=+40 °C
T6
TU=+55 °C
GB