DewPoint too low.
Excessive pressure
drop within the dryer.
The dryer doesn't
drain the condensate.
The dryer
continuously drains
condensate.
Water within the line.
Where installed - The
P
high-pressure
A
switch has been
activated.
Where installed- The
P
low-pressure
B
switch has been
activated.
Where installed -
The T
safety thermo-
S
switch has been
activated.
DMC14- The LED
of the
instrument is on or
flashes to indicate
alarm situations.
The fan is always ON - P
The Hot Gas By-pass Valve is out of setting - contact a refrigeration engineer to restore
the nominal setting.
Ambient temperature is too low - restore de nominal condition.
The Pre-Filter (FTP Series – 3 micron) is clogged - replace the filter element (cartridge) -
Refer to the instructions in the user's and maintenance manual of the filter.
The dryer doesn't drain the condensate - see specific point.
The DewPoint is too low - the condensate is frost and blocks the air - see specific point.
Check for throttling the flexible connection hoses.
The condensate drain service valve is closed - open it.
Verify the electric wiring.
The DewPoint is too low - the condensate is frozen - see specific point.
Bekomat drainer is not operating correctly (see para 5.17 MAINTENANCE
BEKOMAT)
Drainer is dirty – (see para 5.17 MAINTENANCE BEKOMAT)
The dryer doesn't start - see specific point.
Where installed - Untreated air flows through the by-pass unit - close the by-pass.
The dryer doesn't drain the condensate - see specific point.
DewPoint too high - see specific point.
Check which of the following has caused the activation :
1. The ambient temperature is too high or the room aeration is insufficient - provide
proper ventilation.
2. The condenser is dirty - clean it.
3. The condenser fan doesn't work - see specific point.
Reset the pressure-switch pressing the button on the controller itself - verify the
dryer for correct operation.
The PA pressure switch is faulty - contact a refrigeration engineer to replace it.
There is a leak in the refrigerating fluid circuit - contact a refrigeration engineer.
The pressure switch restores automatically when normal conditions are restored -
check the proper operation of the dryer.
Check which of the following has caused the activation :
1. Eccessive thermal load – restore the standard operating conditions.
2. The inlet air is too hot - restore the nominal conditions.
3. The ambient temperature is too high or the room aeration is insufficient - provide
proper ventilation.
4. The condenser unit is dirty - clean it.
5. The fan doesn't work - see specific point.
6. There is a leak in the refrigerating fluid circuit - contact a refrigeration engineer.
Reset the thermo-switch by pressing the button on the thermo-switch itself – verify
the correct operation of the dryer.
The T
thermo-switch is faulty - replace it.
S
The LED
flashes because the DewPoint is too high – see specific point.
The LED
flashes because the DewPoint is too low - see specific point.
The LED
flashes because the probe is faulty or interrupted, the instrument
displays the message "PF" (Probe Failure) – replace the probe.
pressure switch is faulty - replace it.
V
GB