SICK Ex1 Manuel D'utilisation page 40

Table des Matières

Publicité

Fig. 12
Table de configuration du dispositif de mise en surpression F 850S
System identification
FS850S.
Inputs
Language
Structure
Purging
method
Operational
Parameters
Codes
40
Unité d'analyse type «Boîtier industriel Ex1» · Manuel d'utilisation complémentaire · 8013667/ZX77/V 2-3/2018-04 · © SICK AG
Installation no.:
0.6
Production no.:
Description
F850S language
Valve
Solenoid valve type used with
this purging system?
Time based purging method
(Integ N.) or integration purging
method (Integ. Y.)
Continuous flow (C. flow Y.) or
leakage compensation (C. flow
mode
N.)
Purge time
Purge volume
Minimum flow rate during
purging procedure
Minimum flow rate during
normal operation by op. mode
continuous flow
mode continuous flow
Pressure monitor,
minimum pressure
Pressure monitor,
maximum pressure
Set-point pressure during
purging
Set-point pressure during
normal operation
Code for main menu
Code for bypass
Code to enable switching
ignition-capable device
KP Sp = 50.0
KP Sp = 3.0
Modifier le «Code By» sur le lieu d'utilisation en changeant la valeur
(explication → p. 28, §4.1).
SICK
Date:
11.04.1307
Solenoid valve:
Display
Value/ state
Language
Valves
P-Valve
Tick box
Integra.
Integ. Y.
Tick box
Cont. Flow
C. Flow Y.
Tick box
Pur. Time
Pur. Vol.
Min. Fl. P.
Min.Fl. O.
Rated Fl.
Min. Pres.
Max. Pres
R. Pre. Pu.
Rated Pr.
M-Code
By-Code
On/Off-C.
KP Df = 50.0
KP Df = 10.0
Caractéristiques techniques
10.09.04
P.3
BT 8
D-Valve
Integ. N.
C. Flow N.
370 l
0.9 l/s
0.5 l/s
2.0 l/s
0.8 mbar
18 mbar
10 mbar
0001
0002
1000

Publicité

Table des Matières
loading

Table des Matières