LG multi V d'ARUB Serie Manuel D'installation page 88

Table des Matières

Publicité

Circuit imprimé d'unité HR
Setting method of Master indoor unité in zoning
1) Turn dip switch 5,6,10 on at system off.
2) Set the left Ratary switch for HR unité.(Rotary switch No. "0" ➔ HR unité No. "1")
3) Set the right Ratary switch for IDU unité.(Rotary switch No. "0" ➔ HR unité branch No. "1")
4) Display the Master IDU No. of the HR unité on 7segment.(Default display is "00" on 7segment)
5) Press the black button.(The IDU No. increase every 1 second in the zoning )
6) Set the Master IDU(Press the red button during 1.5seconds stop twinkling)
ROTARY 01 ROTARY 02
ATTENTION
• Waiting for 80seconds after power on.
• The zoning information and Master IDU information remove from EEPROM after Auto-addressing.
• If there is installed the central control, it is impossible setting of Master IDU in zoning.
88
Unité extérieure
7 segment
No. of Indoor unité.
No. of HR unité branch.
No. of HR unité.