Internal sensor parameters
Parameter
Name
Hex(Dec)
Process Data
Configuration
Switching
Output (SO)
Binary Data
Channel 1
(BDC2)
Binary Data
Channel 2
(BDC1)
Temperature
Alarm (TA)
Temperature Alarm
Threshold
High Threshold
Low Threshold
Event
Configuration
Temperature
fault event
Temperature
over-run
Temperature
under-run
LED Activation
Max temperature
since start-up
Min temperature
since start-up
Current
temperature
Switching
frequency
Detection counter
22
Rev.01 | IBS04, ICS05, ICS08, ICB12, ICB18, ICB30 Inductive sensors with IO-Link interface | © 2018 | CARLO GAVAZZI Automation
Index
Subindex
Hex(Dec)
0x02(2)
0x04(4)
0x46(70)
0x05(5)
0x08(8)
0x01(1)
0x48(72)
0x02(2)
0x02(2)
0x03(3)
0x4A(74)
0x04(4)
0x4E(78)
0x00(0)
0xCD(205)
0x00(0)
0xCE(206)
0x00(0)
0xCF(207)
0x00(0)
0xD0(208)
0x00(0)
0xD2(210)
0x00(0)
Access
Default value
R/W
1
R/W
0
R/W
0
R/W
0
R/W
100
R/W
-30
R/W
0
R/W
0
R/W
0
R/W
1
R
-
R
-
R
-
R
-
R
-
Data range
0 = SO not shown in PDV
1 = SO shown in PDV
0 = BDC1 not shown in PDV
1 = BDC1 shown in PDV
0 = BDC2 not shown in PDV
1 = BDC2 shown in PDV
0 = TA not shown in PDV
1 = TA shown in PDV
-32768 to 32767 °C
-32768 to 32767 °C
0 = Fault event disabled
1 = Fault event enabled
0 = Warning event disabled
1 = Warning event enabled
0 = Warning event disabled
1 = Warning event enabled
0 = LED indication disabled
1 = LED indication enabled
-32768 to 32767 °C
-32768 to 32767 °C
-32768 to 32767 °C
0 to 32767 Hz
0 to 2147483647
Data Type
(Length)
RecordT16
IntegerT16
IntegerT16
RecordT16
UIntegerT8
IntegerT16
IntegerT16
IntegerT16
IntegerT16
IntegerT32